Sauter flexotron®800
ventilation
Settings
P100012082
77
15.6.2
Alarm delays
Alarm delay, supply air
Al. del. supply air
Control dev: 30 min
High temp: 5 sec
Low temp: 5 sec
Alarm delay, extract air
Al. del. extract air
High temp: 30.0 min
Low temp: 30.0 min
Alarm delay, room
Al. del. room air
High temp: 30.0 min
Low temp: 30.0 min
Alarm delay, frost protection
Alarm delay
Frost prot.: 0 sec
Frost risk: 0 sec
Alarm delay control SAF and EAF
Alarm delay control dev.
pressure
SAF: 30 min
EAF: 30 min
Alarm delay, Humidity
Alarm delay control
deviation humidity 30
Min
Alarm delay, exchanger efficiency
Low efficiency
30 min
Alarm delay, fan malfunction
Alarm delay malfunc.
SAF: 120 sec
EAF: 120 sec
Alarm delay, pump malfunction
Alarm delay malfunc.
P1-Heating: 5 sec
P1-Cooling: 5 sec
P1-Exchan.: 20 sec
Alarm delay, misc.
Alarm delay
Filter mon.: 180 sec
Flow switch: 5 sec
Frost prot.: 0 sec
Ext. Frost prot. DI refers to the digital input signal Deicing Heat exchanger.
Alarm delay, misc. 2