Sauter flexotron®800
ventilation
Settings
P100012082
78
Alarm delay
Deicing DI: 0 sec
Fire alarm: 0 sec
Ext. alarm: 0 sec
Frost protection DI refers to the digital input signal De-icing thermostat
exchanger.
Alarm delay, misc. 3
Alarm delay
Elec. heat: 0 sec
Sensor error: 5 sec
Rot.sent.exch:20 sec
15.6.3
Restore alarm
Service alarm
(filter alarm)
Time counter set to
zero: No
15.7
Save and restore settings
Restore factory
settings: No
Restore user settings: No
In this menu, it is possible to restore all parameters to their factory settings or to the
user settings they were saved as earlier, see below.
Save user settings: No
The present configuration can be saved in a separate memory area and can later be
restored using the previous menu, "Restore user settings".