Sauter flexotron®800
ventilation
Settings
P100012082
73
15
Settings
In this menu group all settings for all activated functions should be available. The menu
group is only available when logging on as Admin. Depending on what choices have
been made during configuration, some of the alternatives in this menu group may not
be shown.
A complete overview of the menu structure is available in section 18.8.
Settings
Control temp
Control pressure
Control flow
Control humidity
Control CO2
Control extra unit
Alarm settings
15.1
Control temp
Supply air controller
Supply air control
P-band: 33.0 °C
I-time: 100.0 sec
The set P-band for the supply air controller is for the whole controller signal. This
means that the P-band for each sequence is proportionate to the split percentage
values given to sequences.
For example:
P-band for the supply air controller is set to 25 K. The split is set so that cooling gets
0…20 % = 20 %, the exchanger gets 30…50 % = 20 % and the heater gets 50…100 %
= 50 %.
The individual P-bands will then be:
Chiller: 20 % of 25°C = 5°C
Exchanger: 20 % of 25°C = 5°C
Heating: 50 % of 25°C = 12.5°C
The remaining 2.5°C are the neutral zone between cooling and exchanger.
The split values are set in the configuration submenu
Other parameters.
See section
16.24.6.
If cascade control
max/min supply setp.
Max: 30°C
Min: 12°C
Room controller
Room control
P-band: 100.0 °C
I-time: 300.0 sec
Extract air controller
Extract air control
P-band: 100.0 °C
I-time: 300.0 sec