Sauter flexotron®800
ventilation
Configuration
P100012082
92
16.22 Running time, 3-position actuators
These parameters have no function if analogue actuators are configured.
The values are used to determine the control parameters for 3-position actuators.
It is important to set correct values since incorrect values lead to sloppy control.
Actuator run time
Heating: 255 sec
Exchanger: 255 sec
Cooling: 255 sec
16.23 Step controllers
Step contr. heating
Step contr. Cooling
16.23.1 Step controller heating
Step controller heating can be set to sequential or binary.
Step contr. heating
Activation levels
Binary steps
Step controller Heating activation levels for sequential control.
For binary control the activation levels are calculated by the controller depending
on the number of steps involved
Start step 1: 10 %
Stop step 1: 5 %
Start step 2: 45 %
Stop step 2: 40 %
Start step 3: 70 %
Stop step 3: 65 %
Start step 4: 95 %
Stop step 4: 90 %
Control parameters. Heater groups is used to calculate activation levels for
binary control. "Hyst." is the switching differential used for each step when
running binary control.
Heater groups: 4
Minimum on/off-
time: 60 sec
Hyst.: 0.5 %