Sauter flexotron®800
ventilation
Configuration
P100012082
83
SAF with EAF slave
If "SAF with EAF slave" has been configured, there is a submenu for setting the CAV
factor, a factor which determines the extract air fan output in relation to the supply air
fan output.
EAF CAV factor:
1.00
For more detailed description, see the section SAF with EAF slave under 5.4.1
Pressure control.
SAF with EAF flow control
If "SAF with EAF flow control" has been configured, there are submenus for setting the
flow calculation factors for "SAF" and "EAF", and the CAV factor for "EAF".
SAF flow control
factors
K-constant: 100
X-constant: 0.50
EAF flow control
factors
K-constant: 100
X-constant: 0.50
EAF CAV factor:
1.00
For more detailed description, see the section SAF with EAF flow control under 5.4.1
Pressure control.
Crosswise interlock between fans
Crosswise interlock means that if one of the fans stops running, the other fan will
automatically stop as well.
Crosswise interlock
between SAF and EAF
No
16.4
Extra control circuit
The extra control circuit can be configured to be either constantly active or to be active
only when the regular control circuit is active.
Mode extra unit
Running if
unit runs