Sauter flexotron®800
ventilation
Configuration
P100012082
107
Type 3
The first line shows the date and time.
The second line shows the present running status.
The third line shows the present temperature setpoint and actual values.
The fourth line shows the present SAF and EAF pressures.
15/03/2004 11:28
System: Running
Sp:22.0°C Act:21.8°C
SAF:1100Pa
EAF:1050Pa
Type 4
The text on the first line can be changed using CASE flexotron®.
The second line shows the date and time.
The third line shows the present running status.
Vent unit 18 PX
2004-03-15 11:28
System: Running
Type 5
The text on the first line can be changed using CASE flexotron®.
The second line shows the date and time.
Vent unit 18 PX
2004-03-15 11:28
16.29.3 Automatic summer-/wintertime change-over
When flexotron®800 is set on automatic summertime/wintertime change-over, the timer
will automatically change between summertime and wintertime according to European
standard.
Automatic summer/
winter time change
over
Yes
16.29.4 Address
The flexotron®800 uses the addresses below when connecting to flexotron®800 tool,
and when multiple controllers are connected in an network. CASE flexotron® normally
uses the addresses below, so if an address is changed, the new address must also be
entered in CASE flexotron®. If several flexotron®800 are connected in a network, all
the units must have the same ELA address, but each unit must have a unique PLA
address.
Address
PLA: 254
ELA: 254
16.29.5 Display anywhere (Remote control)
If multiple flexotron®800 units are connected in a network, it is possible to remote
control a unit in the network from a unit with display. You do this by entering the