Sauter flexotron®800
ventilation
Configuration
P100012082
86
Override of reduced speed for DX cooling
Override to normal quantity of air for DX cooling when the unit runs on reduced quantity
of air. The fans can be set to normal operation when cooling is required at high outdoor
temperatures (e.g. >14°C, the same temperature limit as for blocking of DX cooling).
Force normal
speed if active
DX-cooling:Yes
16.9
Pump control
P1-Heating
P1-Exchanger
P1-Cooling
In these menus the parameters for pump control are set.
If, for any of the control circuits, no output is configured for pump control these settings
will be ignored.
P1 Heating
Pump stop: Yes
Stop delay: 5 min
Outd. Temp stop: 10°C
Differential: 1.0°C
P1 Exchanger
P1-Exchanger
Stop delay: 5 min
P1 Cooling
P1-Cooling
Stop delay: 5 min
For a detailed description of pump functions, see the section Pump control.