Sauter flexotron®800
ventilation
Time settings
P100012082
69
13.2
Timer Normal speed
There are eight separate setting menus, one for each weekday and one extra for
holidays.
Holiday schedules take precedence over other schedules.
For 24 hour running, set a period to 0:00 --- 24:00.
To inactivate a period, set the time to 00:00 --- 00:00. If both periods of a day are set to
0:00 --- 0:00, the unit will not run at 1/1-speed that day.
Normal speed
Monday
Per 1: 07:00 – 16:00
Per.2: 00:00 - 00:00
If you want to run the unit from one day to another, e.g. from Mon 22:00 to Tue 09:00,
the desired running time for both days must be entered.
Normal speed
Monday
Per 1: 07:00 – 16:00
Per.2: 22:00 - 24:00
Normal speed
Tuesday
Per 1: 00:00 – 09:00
Per.2: 00:00 - 00:00
13.3
Timer Reduced speed
These settings will be ignored if single speed fans are configured.
Should periods for normal speed and periods for reduced speed overlap, normal speed
takes precedence.
There are eight separate setting menus, one for each weekday and one extra for
holidays. Holiday schedules take precedence over other schedules. For 24 hour
running, set a period to 00:00 --- 24:00. To disable a period, set it to 00:00 --- 00:00. If
both periods of a day are set to 00:00 --- 00:00, the unit will not run at "Reduced speed"
that day.
Reduced speed
Sunday
Per 1: 10:00 – 16:00
Per.2: 00:00 - 00:00