Function Code List
– PID Function
Code
No.
Function Name
Data Content
Setting
Resoluti
on
Factory
Presets
User
Setting
Value
3014
PID1 feedback value gain
0-50
0.01
1
3015
PID1
control
proportional
gain
(negative:F3012=2)
0-100
0.01
0.1
3016
PID1 control integral time
(negative:F3012=2)
0.01 -100 sec.
0.01s
0.1
3017
PID1 control command value
0-6,000
0.1
0
3018
PID1 control feedback value
(communication function)
0-6,000
0.1
0
3019
Frequency corresponding to PID1
control
maximum command value
0-600Hz
0.01Hz
60
3101
PID2 command value input switching
1: Frequency
2: External analog VIF1 voltage (0
-
5 V)
3: External analog VIF1 voltage (0
-
10 V or potentiometer)
4: External analog VIF2 voltage (0
-
5 V)
5: External analog VIF2 voltage (0
-
10V or potentiometer)
6: External analog VIF3 voltage (0
-
5 V)
7: External analog VIF3 voltage (0
-
10V or potentiometer)
8: External analog VIF1 current (4
-
20mA)
9: External analog VIF2 current (4
-
20mA)
10: External analog VIF3 current (4
-
20mA)
11: Function code setting (F3117)
98:
Pulse train input subPG(option)
99 :Pulse train input
1
1
3102
PID2 feedback input switching
0: No input
1: External analog VIF1 voltage (0
-
5 V)
2: External analog VIF1 voltage (0
-
10 V or potentiometer)
3: External analog VIF2 voltage (0
-
5 V)
4: External analog VIF2 voltage (0
-
10V or potentiometer)
5: External analog VIF3 voltage (0
-
5 V)
6: External analog VIF3 voltage (0
-
10V or potentiometer)
7: External analog VIF1 current (4
-
20mA)
8: External analog VIF2 current (4
-
20mA)
9: External analog VIF3 current (4
-
20mA)
10: Communication mode
98:subPG
feedback PID (option)
99: PG feedback PID
1
0
3103
PID2 control proportional gain
0-100
0.01
0.1
3104
PID2 control integral time
0.01 -100 sec.
0.01s
0.1
3105
PID2 control differential time
0 -100 sec.
0.01s
0
3106
PID2 control integral separation
judgment value
5
-
100% (upper frequency limit reference)
0.1%
100
3107
PID2 feedback signal input filter time
constant
1-500
(
set value 1=10ms
)
.
1
10
3108
Indirect PID2 input reference
5
-
100% (target value reference)
0.1%
20
3109
PID2 deviation limit value
0: No limit
1
-
100% (upper frequency limit reference)
0.1%
100
3110
PID2 output limit value
0: No limit
1
-
100% (upper frequency limit reference)
0.1%
100
3111
PID2 operation polarity switching
1: Command value
-
feedback value
2: Feedback value
-
command value
1
1
3112
PID2 gain polarity switching
1: The plus or minus deviation indicates the same gain
2: The plus or minus deviation indicates different gains
1
1
3113
PID2 command value gain
0-50
0.01
1
3114
PID2 feedback value gain
0-50
0.01
1
3115
PID2 control proportional gain
(negative: F3012=2)
0-100
0.01
0.1
3116
PID2 control integral time
(negative: F3012=2)
0.01 -100 sec.
0.01s
0.1
3117
PID2 control command value
0-6,000
0.1
0
3118
PID2 control feedback value
(communication function)
0-6,000
0.1
0
3119
Frequency corresponding to PID2
control
maximum command value
0-600Hz
0.01Hz
60
3123
PID start mode selection
1: Direct input mode
2: Condition input mode
1
1
3124
PID end mode selection
1: Direct end mode
2: Condition end mode
1
1
3125
PID end setting value
1
-
100% (upper frequency limit standard)
0.1%
20
3127
For factory adjustment
3201
PID control action selection
0: Open loop control
1: PID1 control
2: PID2 control
3: For factory adjustment
4: External terminal switching PID control
5: Timing switch PID control
1
0
3202
For factory adjustment