- 74 -
6-2
Test run
6-2-7
Basic setting (3)
Please set the function codes used for setting the operation command and frequency command.
Table 6-9 Basic function (2)
Function code
Name
Content
Remarks
F1002
1st speed
frequency
setting
selection
1: Operation panel
2: External analog VIF1 voltage (0-5 V)
3: External analog VIF1 voltage (0-10V or potentiometer)
4: External analog VIF2 voltage (0-5 V)
5: External analog VIF2 voltage (0-10V or potentiometer)
6: External analog VIF3 voltage (0-5 V)
7: External analog VIF3 voltage (0-10V or potentiometer)
8: External analog VIF1 current (4-20mA)
9: External analog VIF2 current (4-20mA)
10: External analog VIF3 current (4-20mA)
11: External analog VIF1 vVIF2 voltage
12: External analog VIF1 vVIF3 voltage
13: External analog VIF2 vVIF3 voltage
14: External analog VIF1 voltage -VIF2 voltage
15: External analog VIF2 voltage –VIF1 voltage
16: External analog VIF1 voltage-VIF3 voltage
17: External analog VIF3 voltage –VIF1 voltage
18: External analog VIF1 vVIF2 current
19: External analog VIF1 voltage -VIF2 current
20: External analog VIF1 current -VIF2 voltage
21: Terminal block stepping
22:Communication
25:Pulse train input
26:External analog VIF1 forward / reverse operation
(0 - 10V, 5V reference)
27: External analog VIF2 forward / reverse operation
(0 - 10V, 5V reference)
28:External analog VIF3 forward / reverse operation
(0 - 10V, 5V reference)
Please set the
setting to values
other than 1 when
using control
terminals.
F1101
Operation
command
selection
1: Operation panel
2: External terminal
3: Communication
Note 1) During test run, confirm the factory presets through the operation panel without additional configuration.
Note 2) Before setting external operation signals, check that the control terminals are in OFF (disconnected) state.
Frequency command selection can be switched using the status of multifunctional input terminals. Depending on the
status of multifunctional input 1DFA or 1DFB, the frequency command shall be determined according to the method
set by F1002, or F1034
-
F1036. See F1034
-
F1036.
1DFA terminal
1DFB terminal
1st speed frequency action
OFF
OFF
The method selected by F1002
ON
OFF
The method selected by F1034
OFF
ON
The method selected by F1035
ON
ON
The method selected by F1036