- 39 -
C
h
p
ater
4
4-5
Composition of Control Circuit Terminals
1)
Potentiometer for frequency setting
Please install a 5kΩpotentiometer of 0.3w or above, set the 1st speed frequency and select the frequency
settings of current and voltage by selecting function code F1002.
Please use shielded wires for wiring, please connect one end of the control terminal shield to the shield
terminal ASG, while leave the other end open.
They can be connected to the potentiometer respectively, the power supply terminal of the potentiometer is
the + V common terminal.
The + V terminal can not provide power to the external as it is not a terminal used for supplying power. It is a
dedicated terminal used for connecting the specified potentiometer.
2)
Multifunctional output (open collector output)
The figure below shows an example of using multifunctional output terminals D01 to D03.
※
When using a relay, be sure to install a surge suppressor (reverse-parallel connected diode).
Figure 4-2 Example of using multifunctional output (open collector output)
Note: The maximum output current of the multifunctional output is 50 mA.