- 72 -
6-2
Test run
②
Setting of F5002
-
F5005
Set rated current, frequency, speed and insulation type of the connected motor.
Under normal circumstances, please set according to the motor ratings. If the value set is incorrect, the motor
parameters auto tuning results and the control characteristics of torque control will become adverse.
Note 1):
The settings are interdependent with the settings of motor poles, voltage and capacity (F5001). Therefore, if
F5001 is changed, then function codes F5002 - F5005, F5009 - F5015 which are associated with the motor
parameters will be automatically set with the settings of F5001 as the standard values.
Note 2):
These settings can not be used in V / f control mode.
Note 3):
The special motors shall be set according to F5006 Special Motor Voltage Rating.
(2)
The setting of motor parameter auto tuning mode
Set the auto tuning modes 1 and 2 through F1001 (F1001 = 10 and F1001 = 11). (Check the status of
mechanical system).
・
Please make function code display by pressing the key.
・
After displaying the F1001 in the quick knob, please press the key.
・
Please select the settings in the quick knob.
・
If you want to confirm the settings, please press the key.
(Please Press the key to cancel the setting.)
(3)
Auto tuning starts
Auto tuning will begin if the operation signal is input, and the operation panel displays "TUNE" during this
process and returns to ―Stopped‖ display upon completion of the process. In addition, in auto tuning mode 2,
operation starts in the rotation direction of operation signals until the motor frequency rating (F5003) is
reached, and then operation will continue within 50% of the motor frequency rating.
Press
key to start the auto tuning.
(4)
Motor parameter auto tuning ends
If the auto tuning goes smoothly, then the operation panel will return to the initial interface.
After completion of auto tuning, the parameters obtained through auto tuning will be set into the function code.
(5)
Auto tuning error
①
If the auto tuning fails, then "
. " will be displayed on the operation panel.
During auto tuning, please confirm the contents displayed on operation panel. If a "
" is displayed,
please confirm the following contents and conduct auto tuning again.
• Reconfirm the settings of F5001
-
F5005
• When using special motors, change the range of F5008 if auto tuning is out of range.
Note 1): Enlarging auto tuning range of F5008 will make the error of auto tuning become bigger, therefore please set
appropriate auto tuning range.
②
When using PG sensors, if the detected rotation is in the opposite direction, a ― ‖ will be displayed.
Please confirm the phase of PG pulse. Use operation panel to cancel the ― ‖ warning.
Note 1) Turning up the auto tuning range of F5008 may result in bigger error of auto tuning. Therefore, please set the auto
tuning range.
(6)
Forced ending of auto tuning
The auto tuning mode can be forcibly ended according to stop signal.
Pressing key can also realize forced ending.