- 119 -
-
1
1
9
-
C
h
ap
ter
1
1
11-1 Standard Specification
Item
Specification
Model
(
SVC06-□□□□-
4)
0185
0220
0300
0370
0450
0550
0750
O
u
tp
u
t
spec
ifi
ca
ti
o
n
Mode A
Heavy
overload
Standard applicable motor [kW]
18.5
22
30
37
45
55
75
Rated capacity [kVA] *1
26
32
42
51
62
76
102
Rated current [A] *2
38
46
61
74
90
110
147
Overload current rating *3
150%-1min
Output frequency range *4
0.05-599Hz
(
Starting frequency 0.05-60Hz variable)
Mode B
Light
overload
Standard applicable motor [kW]
22
30
37
45
55
75
90
Rated capacity [kVA] *1
31
41
51
62
76
98
120
Rated current [A] *2
46
61
74
90
110
147
173
Overload current rating *3
120%-1min
Output frequency range *4
0.05-240Hz
(
Starting frequency 0.05-60Hz variable)
Rated output voltage
*5
3
φ
380V-460V
Inp
u
t
p
o
we
r
sup
p
ly
Voltage & Frequency
3
φ
380V-460V, 50/60Hz
Allowable fluctuation
Voltage: -15%, +10% Frequency: ±5% Voltage unbalance: within 3%
Power supply impedance
1% and above
(
Use optional reactor if less than 1%
)
Mode A
Heavy
overload
Required power capacity [kVA] *6
25.4
30.3
40.4
48.1
58.5
72.4
95.4
Input current
[A] *7
With DCL
36.7
43.8
58.3
69.5
84.5
104.5
137.8
Without DCL
Mode B
Light
overload
Required power capacity [kVA] *6
30.3
40.4
48.1
58.5
72.4
95.4
110.5
Input current
[A] *7
With DCL
43.8
58.3
69.5
84.5
104.5
137.8
159.5
Without DCL
Protective structure
Totally enclosed
(
IP20
)
Cooling method
Forced air cooling
Approximate weight
24kg
38kg
47kg
Carrier frequency
Sine wave PWM
(
carrier frequency 1k
-
10kHz
)
*8
DC reactor
Standard(Internal)
*1
Rated capacity at the output voltage of 400V
*2
When input voltage is 400VAC and above, the rated current will be decreased according to the output power
*3
One minute is allowed every 10 minutes
*4
During vector control, PG sensorless is 0.25Hz
-
240Hz /PG sensor is 0.05Hz
-
240Hz (depends on the number of poles)
*5
Output voltage cannot exceed power supply voltage
*6
Vary with the impedance changes of the power supply including a DC reactor
*7
Vary with the impedance of the power supply
*8
The maximum value of carrier frequency varies with the inverter capacity mode and operation status.