- 44 -
4-7
About EMC filter
4-7
About EMC filter
This inverter can be provided with built-in EMC filter (order requirement).
Although the EMC filter can effectively reduce the interference transfer, it will increase the leakage current.
ON or OFF of the EMC filter can be selected as follows through the on / off of the connector.
SVC06-0007 SVC06-0055 SVC06-0110
SVC06-0015 SVC06-0075 SVC06-0150
SVC06-0022
SVC06-0037
SVC06-0040
Before carrying out make-break of the connector, turn the inverter’s input power supply to ―OFF‖ (disconnected)
first, and then check with a circuit tester that no applied voltage is present, and also that the CHARGE lamp is not
lit.
When pulling the connector, pull out the connector while pressing the jack catch of the connector, but do not pull
cable. When inserting it, check if the jack catch has been secured. Please install the connector at ―ON‖ or ―OFF‖.
The EMC filter is set to open (OFF) state at factory.
*When the EMC filter is set to ON, the leakage current will increase.
*Models above 18.5k are provided with only built-in capacitors.
Press the jack catch
,
release lock state
And then the connector can be
pulled freely