- 70 -
6-2
Test run
Before setting the above auto tuning, set the following function codes in order.
Table 6-8 Auto tuning setting
Function Code
Content
Settings
Remarks
F5001
Motor poles, voltage and
capacity
XYZZZ
X: Polarity, Y : Rated voltage
Z: Motor capacity
F5002
Motor current rating
30 - 110% of the inverter
current rating (0.1A stepping)
F5003
Motor frequency rating
10 - 600 Hz
F5004
Motor speed rating
0 -24000 rpm (1rpm stepping)
F5005
Motor insulation type
1: Type A
2: Type E
3: Type B
4: Type F
5: Type H
F5006
The motor’s rated voltage
during auto tuning of motor
parameters
0: Use function code F5001
Selected voltage
100 -460
(the voltage of F5001 is inactive)
F5007
Rated motor slip ratio
0-50%
*If motor parameters are known, please enter the parameters into the following function codes.
F5009 Motor stator resistance (Ω or m Ω)
F5010 Motor rotator resistance (Ω or m Ω)
F5011 Motor stator inductance (mH)
F5012 Motor rotator inductance (mH)
F5013 Motor mutual inductance (mH)
F5014 Motor excitation current (A)
F5015 Motor inertia moment (kgm
2
)
F5016 Load inertia moment ratio