- 30 -
4-4
Composition of Main Circuit Terminals
Model
MCCB
(Leakage
circuit
breaker)
[A]
MC
(Electromagnetic
contactor)
Main circuit
Control
circuit
Rated
current
[A]
Rated
making
current
[A]
Recommended wire size [mm
2
]
S
cre
w d
iam
eter
Tighte
-
ning
torque
[N•m]
Max.
wire
size
[
mm
2
]
S
cre
w d
iam
eter
Max.
wire
size
[mm
2
]
Input
wire
P and P1
wires
Output
wire
g
ro
u
n
d
in
g
wire
SVC06-2200-
4
600
600
660
150×2(200)
250×2(200)
150×2(200)
60
M16
100
-
M3
1.25
SVC06-2500-
4
700
600
660
200×2(200)
250×2(200)
200×2(200)
60
Note 1: The values for wires in the main circuit are for 600 V IV PVC-insulated wires (60ºC) when the inverter ambient
temperature is 40ºC. The values in parentheses are for 600 V bridged-polyethylene insulated wires (90ºC).
Note 2: The maximum wire size indicates the maximum wire cross-sectional area that can be used with the terminal block.
Note 3: If possible, use thick and short conductors for grounding wire.
※
To be compliant with the European Directive (Low Voltage Directive), earth (ground) the inverter
according
to the instructions on table 14-1.