- 16 -
3-2
Installation Direction and Space
3-2
Installation Direction and Space
(1) This inverter is of the wall mounting type.
(2) Install the inverter vertically on a flat mounting surface.
(3) Since the inverter generates heat, provide adequate space around it to ensure good heat dissipation
conditions.
(4) When installing the inverter in a control cabinet, provide a ventilation fan to keep the ambient temperature
below 40°C.
(5) When installing the inverter in a control cabinet, mounting the radiator fins outside the control cabinet will
help to reduce the internal temperature of the cabinet.
(6) This inverter is of IP20 structure.
Please select according to intended use.
Figure 3-1 Surrounding Space
Figure 3-2 Arranging method of radiator fins outside the cabinet
When several inverters are set in a control cabinet, be sure to locate the ventilation fans properly to
allow free air circulation.
If the ventilation fans are located improperly, the ambient temperature will rise and affect the cooling
of the inverter.
Ven
Inside cabinet
Inside cabinet
Inside cabinet
Inside cabinet
(Correct)
(Incorrect)
(Correct)
(Incorrect)
Figure 3-3 Arranging method inside the cabinet
Figure 3-4 Ventilation fan position in cabinet
Above 10cm
Above 10cm
Above 5cm
Above 5cm
Ventilation fan
Ventilation fan
Cooling air
Cooling air