Piping Diagram
Samsung Electronics
267
Electronic Expansion Valve(EEV) Control
▪
Purpose
General control: Maintain the amount of refrigerant flowing into the indoor units at the appropriate level.
Inactive indoor unit control: Prevent insufficient refrigerant due to refrigerant stagnating in the piping connected to inactive
indoor units.
▪
Concept
General control: Control is performed with the superheat degree in cooling mode. In heating mode, control is performed
with the subcooling degree.
Inactive indoor unit control: The gas pipe is kept open slightly in heating mode to prevent refrigerant from stagnating in the
piping.
▪
Control specifications in detail
∙
Condition(s) required to use modes
- General control : Thermos on indoor units are on
- Inactive indoor unit EEV control: (Comp OFF) or (Comp ON and Indoor unit Thermo-OFF)
∙
Operation specifications
- General control: Control is performed with the superheat degree at the exit of indoor heat exchanges in cooling mode. In
heating mode, control is performed with the subcooling degree.
- Inactive indoor unit EEV control: Control is performed as shown in the following table.
Outdoor unit operation
COMP ON
COMP OFF
Indoor unit operation
Cooling
Heating
COMP stops
- 3 min
COMP stops
3 - 5 min
COMP stops
5 min elapses
(Auto) cooling /
Dehumidification /
Fan
Thermo On
Cooling EEV control
0
0
35
Thermo Off
0
Note 1*
0
0
35
(Auto) heating
Operation On
Heating EEV control
35
35
35
Operation Off
0
Note 1*
35
35
35
* Note 1 : Control of inactive heating units (lower noise/general)
Outdoor unit for first priority
outdoor unit
CAM
EDM high-head
EDM general
0
℃
or lower
80
130
200
Above 0
℃
80
120
180
Cooling
Condensed liquid
Gas
Hot gas
Condensed liquid
Heating
7-3 Functions (cont.)
7-3-2-6 Indoor unit control (cont.)
7-3-2 Control (cont.)
Содержание AM072BXV Series
Страница 141: ...Troubleshooting Samsung Electronics 135 4 3 Appropriate Measures for Different Symptom cont...
Страница 160: ...Samsung Electronics 154 Troubleshooting 4 4 2 Pump down operation cont 4 4 Case study for trouble shoots cont...
Страница 162: ...Samsung Electronics 156 Troubleshooting 4 4 3 Pump out operation cont 4 4 Case study for trouble shoots cont...
Страница 190: ...PBA Diagram and Parts List Samsung Electronics 184 5 8 PF8 Inv Integration J POWER 1 2 3 4 5 6 1 7 8 12 11 10 9...
Страница 192: ...PBA Diagram and Parts List Samsung Electronics 186 5 9 PF8 Inv Integration F POWER 1 2 3 4 5 6 11 10 9 12 1 7 8...
Страница 200: ...Samsung Electronics 194 Wiring Diagram This Document can not be usedwithout Samsung s authorization 6 3 AM162BXVGF AA...
Страница 201: ...Samsung Electronics 195 Wiring Diagram 6 4 AM192BXVGJ AA This Document can not be usedwithout Samsung s authorization...