Samsung Electronics
64
Troubleshooting
4-2 Service Operation
4-2-1 Special Operation
►
Setting key operation and checking the view mode with tact switch
►
Key input of the outdoor unit when the service enters the operation mode.
K1 control
KEY operation
Display on segment
Press and hold 1 time
Auto trial operation
“K”“K”“BLANK”“BLANK”
K1
(Number of press)
KEY operation
Display on segment
1 time
Refrigerant charging in Heating mode
“K”“1”“BLANK”“BLANK”
2 times
Trial operation in Heating mode
“K”“2”“BLANK”“BLANK”
3 times
Pump out in Heating mode (Outdoor unit address 1)
“K”“3”“BLANK”“1”
4 times
Pump out in Heating mode (Outdoor unit address 2)
“K”“3”“BLANK”“2”
5 times
Pump out in Heating mode (Outdoor unit address 3)
“K”“3”“BLANK”“3”
6 times
Pump out in Heating mode (Outdoor unit address 4)
“K”“3”“BLANK”“4”
7 times
Vaccuming (Outdoor unit address 1)
“K”“4”“BLANK”“1”
8 times
Vaccuming (Outdoor unit address 2)
“K”“4”“BLANK”“2”
9 times
Vaccuming (Outdoor unit address 3)
“K”“4”“BLANK “ “3”
10 times
Vaccuming (Outdoor unit address 4)
“K”“4”“BLANK”“4”
11 times
Vaccuming (All outdoor units)
“K”“4”“BLANK”“A”
12 times
Inverter Fault Detection(Comp#1)
“K”“5”“I”“1”
13 times
Inverter Fault Detection(Comp#2)
“K”“5”“I”“1”
14 times
Inverter Fault Detection(Fan#1)
“K”“5”“F”“1”
15 times
Inverter Fault Detection(Fan#2)
“K”“5”“F”“2”
16 times
End Key operation
-
• After installing the product, be sure to perform leak tests on the piping connections. After pumping down refrigerant to inspect or relocate the outdoor
unit, be sure to stop the compressor and then remove the connected pipes.
- Do not operate the compressor while a valve is open due to refrigerant leakage from a pipe or an unconnected or incorrectly
connected pipe. Failure to do so may cause air to flow into the compressor and too a high pressure to develop inside the refrigerant circuit, leading to an
explosion or product malfunction.
WARNING
Содержание AM072BXV Series
Страница 141: ...Troubleshooting Samsung Electronics 135 4 3 Appropriate Measures for Different Symptom cont...
Страница 160: ...Samsung Electronics 154 Troubleshooting 4 4 2 Pump down operation cont 4 4 Case study for trouble shoots cont...
Страница 162: ...Samsung Electronics 156 Troubleshooting 4 4 3 Pump out operation cont 4 4 Case study for trouble shoots cont...
Страница 190: ...PBA Diagram and Parts List Samsung Electronics 184 5 8 PF8 Inv Integration J POWER 1 2 3 4 5 6 1 7 8 12 11 10 9...
Страница 192: ...PBA Diagram and Parts List Samsung Electronics 186 5 9 PF8 Inv Integration F POWER 1 2 3 4 5 6 11 10 9 12 1 7 8...
Страница 200: ...Samsung Electronics 194 Wiring Diagram This Document can not be usedwithout Samsung s authorization 6 3 AM162BXVGF AA...
Страница 201: ...Samsung Electronics 195 Wiring Diagram 6 4 AM192BXVGJ AA This Document can not be usedwithout Samsung s authorization...