Piping Diagram
Samsung Electronics
203
No
Part Name
Abbreviation
Symbol
Function
19
MainCooling Valve
(Solenoid valve-Main Cooling)
V_MC
Opening the valve during cooling operation and sends
a high-pressure gas into the indoor unit for the heating
operation. (HR Only)
20
Accumulator Oil Return Valve
(Solenoid valve-Accumulator Oil
Return)
V_AR
Opening the valve during operation and sends the oil which
accumulates in the lower liquid separator to the compressor.
21
4Way Valve
(Solenoid valve-4Way)
V_4W
It determines the cooling / heating operation mode.
(The valve signal when the heating operation is ON)
22
Discharge Temp. Sensor
(Thermistor-Discharge pipe)
T_D
Measure the temperature of the compressor discharge pipe.
It is mainly used to protect the compressor.
23
Suction Temp. Sensor
(Thermistor-Suction pipe)
T_S
Measure the temperature of the compressor suction line.
It is used to determine the suction superheat of the
compressor.
24
Cond Out Temp. Sensor
(Thermistor-Cond Out)
T_CO
Measure the liquid pipe temperature of the heat exchanger.
Used to enter in defrosting operation and escape judgment.
25
EVI In Temp. Sensor
(Thermistor-EVI In)
T_EI
Measure the temperature of the intercooler inlet pipe (EVI
EEV side). It is used to determine the superheat of the EVI
In / Out.
26
EVI Out Temp. Sensor
(Thermistor-EVI Out)
T_EO
Measure the temperature of the intercooler outlet pipe (EVI
EEV side). It is used to determine the superheat of the EVI
In / Out.
27
Liquid Tube Temp. Sensor
(Thermistor-Liquid pipe)
T_L
Measure the temperature of the outdoor liquid pipe.
It is used to determine the supercooling.
28
Comp. Top Temp. Sensor
(Thermistor-Compressor Top)
T_CT
To measure the surface temperature of the compressor Top
Cover. It is mainly used to protect the compressor.
29
Ambient Temp. Sensor
(Thermistor-Ambient)
T_A
Measure the temperature of the outdoor air.
■
Cycle component Symbol and Function (cont.)
7-1 Piping Diagram (cont.)
Содержание AM072BXV Series
Страница 141: ...Troubleshooting Samsung Electronics 135 4 3 Appropriate Measures for Different Symptom cont...
Страница 160: ...Samsung Electronics 154 Troubleshooting 4 4 2 Pump down operation cont 4 4 Case study for trouble shoots cont...
Страница 162: ...Samsung Electronics 156 Troubleshooting 4 4 3 Pump out operation cont 4 4 Case study for trouble shoots cont...
Страница 190: ...PBA Diagram and Parts List Samsung Electronics 184 5 8 PF8 Inv Integration J POWER 1 2 3 4 5 6 1 7 8 12 11 10 9...
Страница 192: ...PBA Diagram and Parts List Samsung Electronics 186 5 9 PF8 Inv Integration F POWER 1 2 3 4 5 6 11 10 9 12 1 7 8...
Страница 200: ...Samsung Electronics 194 Wiring Diagram This Document can not be usedwithout Samsung s authorization 6 3 AM162BXVGF AA...
Страница 201: ...Samsung Electronics 195 Wiring Diagram 6 4 AM192BXVGJ AA This Document can not be usedwithout Samsung s authorization...