![Samsung AM072BXV Series Скачать руководство пользователя страница 82](http://html1.mh-extra.com/html/samsung/am072bxv-series/am072bxv-series_service-manual_4738778082.webp)
Samsung Electronics
76
Troubleshooting
■
Diagnosis and Adjustment (Error Code)
►
Error code related to the Communications / Settings / HW
(cont.)
Error mode
Cause
E-447
Motor wire of Fan1 is not connected
E-448
Lock error on Fan1
E-452
Error due to ZPC detection circuit problem or power failure
E-453
Error due to overheated motor of outdoor unit's Fan1
E-454
Error due to the outdoor unit fan RPM
E-455
Error due to the over heat Fan1 IPM
E-457
Outdoor unit Reversed direction of the wind Error
E-461
Error due to operation failure of inverter compressor 1
E-462
Compressor stop due to full current control
E-464
Error due to over-current of inverter compressor 1
E-465
Overload error of inverter compressor 1
E-466
Error due to over voltage /low voltage of Inverter PBA1
E-467
Error due to unconnected wire of compressor 1
E-468
Output current sensor error of inverter PBA1
E-469
DC voltage sensor error of inver PBA1
E-471
Error due to an abnormal EEPROM of inverter 1
E-474
Heat sink temperature sensor error of inverter PBA1
E-478
Error due to overcurrent of Fan1
E-485
Error due to input current of inverter 1
E-486
Error due to over voltage/low voltage of Fan
E-487
Hall IC connection error of Fan1/Two motor parameter difference error
E-489
Overload error of Fan1
E-491
Error due to an abnormal EEPROM of Fan1
E-493
Output current sensor error of Fan1
E-496
DC voltage sensor error of Fan1
E-499
Heat sink temperature sensor error of Fan1
E-500
Error due to overheat caused by contact failure on IPM of Inverter PBA1
E-503
Error due to alert the user to check if the service valve is closed
E-504
Error due to self diagnosis of compressor operation
E-505
Error due to self diagnosis of high pressure sensor
E-506
Error due to self diagnosis of low pressure sensor
E-554
Leakage of refrigerant (In case the refrigerant is leaked)
E-560
Outdoor unit's option switch setting error (Using E2P option of other models or emergency operation for
compressor malfunction option setting was enabled on all compressors of corresponding outdoor unit )
E-563
Error due to module installation of indoor unit with old version (Micom version needs to be checked)
E-573
Error due to using single type outdoor unit in a module installation
E-574
Leakage of refrigerant(In case the amount of refrigerant charge is insufficient or the refrigerant is leaked)
E-702
Error due to closed EEV of indoor unit (1st detection)
E-703
Error due to opened EEV of indoor unit (1st detection)
E-901
EHS water in sensor(Short or Open)
E-902
EHS water out sensor(Short or Open)
4-2 Service Operation (cont.)
4-2-3 Number Display Method (Outdoor Unit, MCU, Cable remote control, wall-mount, etc.)
Содержание AM072BXV Series
Страница 141: ...Troubleshooting Samsung Electronics 135 4 3 Appropriate Measures for Different Symptom cont...
Страница 160: ...Samsung Electronics 154 Troubleshooting 4 4 2 Pump down operation cont 4 4 Case study for trouble shoots cont...
Страница 162: ...Samsung Electronics 156 Troubleshooting 4 4 3 Pump out operation cont 4 4 Case study for trouble shoots cont...
Страница 190: ...PBA Diagram and Parts List Samsung Electronics 184 5 8 PF8 Inv Integration J POWER 1 2 3 4 5 6 1 7 8 12 11 10 9...
Страница 192: ...PBA Diagram and Parts List Samsung Electronics 186 5 9 PF8 Inv Integration F POWER 1 2 3 4 5 6 11 10 9 12 1 7 8...
Страница 200: ...Samsung Electronics 194 Wiring Diagram This Document can not be usedwithout Samsung s authorization 6 3 AM162BXVGF AA...
Страница 201: ...Samsung Electronics 195 Wiring Diagram 6 4 AM192BXVGJ AA This Document can not be usedwithout Samsung s authorization...