Troubleshooting
Samsung Electronics
171
4-4-14 Case study – Related error with IPM
Error code
E500 (INV 1) / E400 (INV 2)
Contents
IGBT module over heated error
Error result
Possibility
1) Loose screw connection between IGBT module and heat sink
2) No thermal grease on Heat sink
3) Defect of related electronic component
Treatment
1) Check status of screws on IGBT module
2) Plastering thermal grease to IGBT module or heat sink
3) Change INV PBA
Heat sink
IGBT(IPM) module
Inv. PBA
Good
No Good
4-4 Case study for trouble shoots (cont.)
Содержание AM072BXV Series
Страница 141: ...Troubleshooting Samsung Electronics 135 4 3 Appropriate Measures for Different Symptom cont...
Страница 160: ...Samsung Electronics 154 Troubleshooting 4 4 2 Pump down operation cont 4 4 Case study for trouble shoots cont...
Страница 162: ...Samsung Electronics 156 Troubleshooting 4 4 3 Pump out operation cont 4 4 Case study for trouble shoots cont...
Страница 190: ...PBA Diagram and Parts List Samsung Electronics 184 5 8 PF8 Inv Integration J POWER 1 2 3 4 5 6 1 7 8 12 11 10 9...
Страница 192: ...PBA Diagram and Parts List Samsung Electronics 186 5 9 PF8 Inv Integration F POWER 1 2 3 4 5 6 11 10 9 12 1 7 8...
Страница 200: ...Samsung Electronics 194 Wiring Diagram This Document can not be usedwithout Samsung s authorization 6 3 AM162BXVGF AA...
Страница 201: ...Samsung Electronics 195 Wiring Diagram 6 4 AM192BXVGJ AA This Document can not be usedwithout Samsung s authorization...