Piping Diagram
Safety Start – Normal Start
▪
Purpose
Stable start-up in a low-temperature section with overload
▪
Concept
Compressors start in sequential order to ensure stable operation if the indoor unit operation ratio is low or there is an overload.
▪
Control specifications in detail
-
Condition(s) required to enter Normal Start mode : None of the conditions required to enter Quick Start mode are satisfied.
- In Normal Start mode, compressors are controlled as shown below.
(See the chart below for conditions required to complete specific steps)
- Condition(s) required to enter Normal Operation mode : [ A or B ]
A. DSH > 10 K
B. Max (Tdis, Ttop) ≥ 30
℃
- Cold Operation mode will activate if none of the conditions required to enter Normal Operation mode are satisfied.
- In Cold Operation mode, the compressor frequency increase speed is restricted to 1Hz per 30 sec.
- Condition(s) required to close Cold Operation mode: [ A or B ]
A. A maximum of 30 min has elapsed
B. DSH > 15 K
7-3 Functions (cont.)
7-3-2-2 Start-up modes (cont.)
7-3-2 Control (cont.)
Содержание AM072BXV Series
Страница 141: ...Troubleshooting Samsung Electronics 135 4 3 Appropriate Measures for Different Symptom cont...
Страница 160: ...Samsung Electronics 154 Troubleshooting 4 4 2 Pump down operation cont 4 4 Case study for trouble shoots cont...
Страница 162: ...Samsung Electronics 156 Troubleshooting 4 4 3 Pump out operation cont 4 4 Case study for trouble shoots cont...
Страница 190: ...PBA Diagram and Parts List Samsung Electronics 184 5 8 PF8 Inv Integration J POWER 1 2 3 4 5 6 1 7 8 12 11 10 9...
Страница 192: ...PBA Diagram and Parts List Samsung Electronics 186 5 9 PF8 Inv Integration F POWER 1 2 3 4 5 6 11 10 9 12 1 7 8...
Страница 200: ...Samsung Electronics 194 Wiring Diagram This Document can not be usedwithout Samsung s authorization 6 3 AM162BXVGF AA...
Страница 201: ...Samsung Electronics 195 Wiring Diagram 6 4 AM192BXVGJ AA This Document can not be usedwithout Samsung s authorization...