Rotation defrost operation
▪
Purpose
Activate defrost mode on module-installed HR outdoor units in sequential order to improve heating efficiency.
▪
Concept
-
Defrost operation is performed on outdoor units in sequential order when main heating mode is active on HR outdoor units.
- If rotational defrost mode is used 3 times consecutively, defrost operation will be performed on all the outdoor units when defrost
mode is turned on again.
▪
Control specifications in detail
- Enabled only when rotational defrost mode has been enabled by the Key option.
- Rotational defrost operation is performed in the following cases: two or more outdoor units are installed, the outdoor tempera
-
ture is -5
℃
or higher, rotational defrost has not been performed 3 times consecutively, the previous defrost mode was a general
defrost, or the duration of rotational defrost < the quantity of indoor units x 10 min.
- For the sequence of rotational defrost, the order of priority for outdoor units is followed.
- For the temperature and time conditions required to enter defrost mode, the same conditions as general defrost mode are applied.
- Condition(s) required to turn off defrost mode: Cond out temp ≥ 15
℃
OR 12 min after defrost mode has started.
Actuator
Outdoor units in defrost mode
Units not being in defrost mode
Compressor
Depends on the outdoor unit capacity
(86-110Hz)
General control
Outdoor EEV
Full close
General control
Outdoor Fan
0 step
General control
HR EEV
Off
General control
Main cooling valve
ON
General control
Indoor
EEV
Cooling indoor
unit
Active unit
General control
Inactive unit
Required step for control of the superheat degree
Heating
Active unit
General control
Indoor unit
Inactive unit
General control on inactive units
Indoor
Fan
Cooling indoor
unit
Active unit
General control
Inactive unit
Set fan speed
Heating
Active unit
Mid fan speed
Indoor unit
Inactive unit
Off
Time
Maximum of 12 min
-
7-3 Functions (cont.)
7-3-2-4 Special operation modes (cont.)
7-3-2 Control (cont.)
Содержание AM072BXV Series
Страница 141: ...Troubleshooting Samsung Electronics 135 4 3 Appropriate Measures for Different Symptom cont...
Страница 160: ...Samsung Electronics 154 Troubleshooting 4 4 2 Pump down operation cont 4 4 Case study for trouble shoots cont...
Страница 162: ...Samsung Electronics 156 Troubleshooting 4 4 3 Pump out operation cont 4 4 Case study for trouble shoots cont...
Страница 190: ...PBA Diagram and Parts List Samsung Electronics 184 5 8 PF8 Inv Integration J POWER 1 2 3 4 5 6 1 7 8 12 11 10 9...
Страница 192: ...PBA Diagram and Parts List Samsung Electronics 186 5 9 PF8 Inv Integration F POWER 1 2 3 4 5 6 11 10 9 12 1 7 8...
Страница 200: ...Samsung Electronics 194 Wiring Diagram This Document can not be usedwithout Samsung s authorization 6 3 AM162BXVGF AA...
Страница 201: ...Samsung Electronics 195 Wiring Diagram 6 4 AM192BXVGJ AA This Document can not be usedwithout Samsung s authorization...