Samsung Electronics
132
Troubleshooting
4-3 Appropriate Measures for Different Symptom
(cont.)
4-3-46
/
COMP Overcurrent error (cont.)
Continue
Continue
Before change / After change
Error, depending on the situation replace
the Compressor or PBA
■
Compressor applied one
■
Compressor applied two
Restart
Inverter1- Compressor2
Inverter2- Compressor1 to the wiring change
Power Off
Replace Inverter PBA
Before change
After change
Measure
E464
E464
Replace No.1Inverter PBA
E464
E364
Replace No.1 Compressor
E364
E364
Replace No.2 Inverter PBA
E364
E464
Replace No.2 Compressor
See the "Contain of compressor Exchange (3-XX)" in service manual when you replace the compressor.