Troubleshooting
Samsung Electronics
67
4-2 Service Operation (cont.)
4-2-1 Special Operation (cont.)
■
Auto Trial Operation
►
After initial installation, stable operation for a certain period of time limited to operation conditions.
Cooling
Heating
Method of Entry
K2 Tact Switch twice
K1 Tact Switch twice
Compressor
Normal operation, but the maximum frequency limit (differ by model)
Indoor Unit
Whole operation (The set temperature=3°C)
Whole operation (The set temperature=40°C)
Outdoor fan and valves
Normally control conduct
Operation time
Min : 60 minutes, Max : 10 hours
Etc.
• Exceed the maximum operating time at stops and waits.
• Protection and control, self-diagnosis is performed.
■
Refrigerant filling operation
►
Operation to filling the refrigerant compressor was fixed at a certain frequency.
Cooling
Heating
Method of Entry
K2 Tact Switch one time
K1 Tact Switch one time
Compressor
Starting frequency (Mild Start frequency) operation
Indoor Unit
Whole operation (The set temperature=3°C)
Whole operation (The set temperature=40°C)
Outdoor fan and valves
Normally control conduct
Operation time
60 minutes
Etc.
During the filling operation does not enter the special operation, such as oil recovery, defrost.
■
Heating Pump Out
►
Operation for the repair of the Individual outdoor unit, the outdoor unit refrigerant emissions to the indoor part.
►
Liquid pipe service valve and the gas pipe service valve operation, the operator manually need to close.
►
Observe low pressure using View Mode of K4 button if compressor operate.
If low pressure goes down below about 0.2 MPa.g : Immediately lock the gas side service valve, Pump Out operation is shut down.
(Pump out operation shut down : K1 button once more press or K3 button one time press)
►
If operation of low pressure goes down below 0.1 MPa.g : Will be stopped automatically for the protection of the compressor.
How to Initiate
K1 Tact Switch 3 times~6 times
Compressor
60Hz
Indoor Unit
Whole Operation (The set temperature=40°C)
4Way Valve
ON (Heating Mode)
Outdoor Fan
Maximum air flow
Main EEV
Operation side : 700 Step (Stop side : 0 step)
Maximum Operation Time
10 minutes
Protection Control
Conduct the discharge temperature, high pressure control. (Low pressure protection control is not carried out)
※ Low pressure is outside normal limits : Operation is shut down after gas pipe manually closed.
Etc.
Entry after safety start. (Only the corresponding Outdoor Unit operation.)
To pump out more than 2 : Except communication between Outdoor Unit of relevant set after working for one,
remainder set makes Pump Out add.
Содержание AM072BXV Series
Страница 141: ...Troubleshooting Samsung Electronics 135 4 3 Appropriate Measures for Different Symptom cont...
Страница 160: ...Samsung Electronics 154 Troubleshooting 4 4 2 Pump down operation cont 4 4 Case study for trouble shoots cont...
Страница 162: ...Samsung Electronics 156 Troubleshooting 4 4 3 Pump out operation cont 4 4 Case study for trouble shoots cont...
Страница 190: ...PBA Diagram and Parts List Samsung Electronics 184 5 8 PF8 Inv Integration J POWER 1 2 3 4 5 6 1 7 8 12 11 10 9...
Страница 192: ...PBA Diagram and Parts List Samsung Electronics 186 5 9 PF8 Inv Integration F POWER 1 2 3 4 5 6 11 10 9 12 1 7 8...
Страница 200: ...Samsung Electronics 194 Wiring Diagram This Document can not be usedwithout Samsung s authorization 6 3 AM162BXVGF AA...
Страница 201: ...Samsung Electronics 195 Wiring Diagram 6 4 AM192BXVGJ AA This Document can not be usedwithout Samsung s authorization...