Piping Diagram
Points of Refrigerant Control (Cooling Operation)
Cooling mode is affected by the quantity, capacity, and fan speed of active indoor units. Indoor air temperature and humidity
also affect the mode.
▪
Adjusting the compressor capacity
Adjust the compressor speed to match the evaporation pressure to the target pressure. Evaporation pressure is measured
by the low pressure sensor on the outdoor unit in order to adjust the cooling capacity according to load.
▪
Adjust the indoor unit EEV to sync the refrigerant superheated degree for the indoor heat exchanger (formula: exit refriger-
ant temperature - entrance refrigerant temperature) with the target superheated degree.
7-3 Functions (cont.)
7-3-1 Basics (cont.)
7-3-1-2 Refrigeration Cycle (cont.)
Содержание AM072BXV Series
Страница 141: ...Troubleshooting Samsung Electronics 135 4 3 Appropriate Measures for Different Symptom cont...
Страница 160: ...Samsung Electronics 154 Troubleshooting 4 4 2 Pump down operation cont 4 4 Case study for trouble shoots cont...
Страница 162: ...Samsung Electronics 156 Troubleshooting 4 4 3 Pump out operation cont 4 4 Case study for trouble shoots cont...
Страница 190: ...PBA Diagram and Parts List Samsung Electronics 184 5 8 PF8 Inv Integration J POWER 1 2 3 4 5 6 1 7 8 12 11 10 9...
Страница 192: ...PBA Diagram and Parts List Samsung Electronics 186 5 9 PF8 Inv Integration F POWER 1 2 3 4 5 6 11 10 9 12 1 7 8...
Страница 200: ...Samsung Electronics 194 Wiring Diagram This Document can not be usedwithout Samsung s authorization 6 3 AM162BXVGF AA...
Страница 201: ...Samsung Electronics 195 Wiring Diagram 6 4 AM192BXVGJ AA This Document can not be usedwithout Samsung s authorization...