5) Ball valve (service valve)
∙
What to inspect: Status of the outdoor unit's ball valve (service valve)
∙
Error code: E503 ("NG" is indicated in the result report)
∙
How to determine error: Check the variations of the operation frequency and pressure on the compressors during
operation.
∙
Perform inspection according to the steps shown below.
■
Precautions
- If an error occurs, Auto Trial Operation stops immediately.
- When inspecting the ball valve, inspect the liquid line, gas line, and high pressure line (HR only) together.
- Symptoms in the event of an issue on the 4-way valve
A. Abnormal noise during compressor operation
B. Increase in the suction temperature
C. See the troubleshooting instructions on NG items related to the 4-way valve
- Symptoms in the event of an issue on the Main EEV
A. It is not possible to control the superheat (SH)
B. It is not possible to secure a DSH of higher than 20K
C. See the troubleshooting instructions on NG items related to the Main EEV
- If any abnormality occurs on the pressure sensor, see the troubleshooting instructions on NG items related to the pressure sensor
- If there frost has formed on the outdoor heat exchanger, perform Trial Operation or forced defrost operation to eliminate the frost, and
then perform Auto Trial Operation again.
- To replace a component or inspect the PBA, be sure to cut off the power supply first.
If inspection must be performed with the power supply on, exercise extra care to prevent electric shock.
Take corrective measures.
Take corrective measures.
Take corrective measures.
Take corrective measures.
Is the ball valve
on the outdoor unit opened?
Has the correct
amount of additional refrigerant been injected
into the indoor unit and liquid
line?
Is the operation cycle normal?
Are the 4-way valve,
Main EEV and pressure sensors operating
properly?
Perform Trial Operation (cooling/heating)
- See the instructions on Key operation modes.
Perform Auto Trial Operation again.
Yes
No
No
No
No
9-1 Auto Trial Operation (cont.)
9-1-3 How to resolve NG items (cont.)
Содержание AM072BXV Series
Страница 141: ...Troubleshooting Samsung Electronics 135 4 3 Appropriate Measures for Different Symptom cont...
Страница 160: ...Samsung Electronics 154 Troubleshooting 4 4 2 Pump down operation cont 4 4 Case study for trouble shoots cont...
Страница 162: ...Samsung Electronics 156 Troubleshooting 4 4 3 Pump out operation cont 4 4 Case study for trouble shoots cont...
Страница 190: ...PBA Diagram and Parts List Samsung Electronics 184 5 8 PF8 Inv Integration J POWER 1 2 3 4 5 6 1 7 8 12 11 10 9...
Страница 192: ...PBA Diagram and Parts List Samsung Electronics 186 5 9 PF8 Inv Integration F POWER 1 2 3 4 5 6 11 10 9 12 1 7 8...
Страница 200: ...Samsung Electronics 194 Wiring Diagram This Document can not be usedwithout Samsung s authorization 6 3 AM162BXVGF AA...
Страница 201: ...Samsung Electronics 195 Wiring Diagram 6 4 AM192BXVGJ AA This Document can not be usedwithout Samsung s authorization...