Samsung Electronics
270
Piping Diagram
Emergency operation for compressor malfunction
▪
Purpose
Perform emergency operation until servicing if there is compressor failure when using more than one compressor.
▪
Concept
Faulty compressors are disabled and turned off.
▪
Control specifications in detail
Disabled compressors are excluded from capacity distribution, heat treatment of winding wire, protective control, and self-
diagnosed error detection.
▪
Notes
-
The performance may degrade if this option is changed.
- Make sure to return the option to the default value after servicing the compressor.
- Error E560 will be triggered if all the compressors on outdoor units are disabled.
(The SVC V/V must be closed for outdoor units if modules are installed and all the compressors on a single outdoor unit
are disabled.)
Setting Outdoor
Seg1
Seg2
Seg3
Seg4
Emergency operation for compressor malfunction
Individual
0
0
0
0
Disabled (Default)
0
1
Set compressor 1 as malfunction state
0
2
Set compressor 2 as malfunction state
7-3 Functions (cont.)
7-3-3-1 Field Setting
7-3-3 Others
Содержание AM072BXV Series
Страница 141: ...Troubleshooting Samsung Electronics 135 4 3 Appropriate Measures for Different Symptom cont...
Страница 160: ...Samsung Electronics 154 Troubleshooting 4 4 2 Pump down operation cont 4 4 Case study for trouble shoots cont...
Страница 162: ...Samsung Electronics 156 Troubleshooting 4 4 3 Pump out operation cont 4 4 Case study for trouble shoots cont...
Страница 190: ...PBA Diagram and Parts List Samsung Electronics 184 5 8 PF8 Inv Integration J POWER 1 2 3 4 5 6 1 7 8 12 11 10 9...
Страница 192: ...PBA Diagram and Parts List Samsung Electronics 186 5 9 PF8 Inv Integration F POWER 1 2 3 4 5 6 11 10 9 12 1 7 8...
Страница 200: ...Samsung Electronics 194 Wiring Diagram This Document can not be usedwithout Samsung s authorization 6 3 AM162BXVGF AA...
Страница 201: ...Samsung Electronics 195 Wiring Diagram 6 4 AM192BXVGJ AA This Document can not be usedwithout Samsung s authorization...