Troubleshooting
Samsung Electronics
119
4-3-38
Prevention of heating refrigerant charge due to outdoor temperature
Outdoor unit
display
Indoorunit
display
Duct, Cassette (1/2 Way),Console, Celing
Cassette (4/Mini4 Way)
Wall-mounted (NeoForte)
Operation Defrost Timer Fan Filter/
MPI Operation Defrost Timer Filter Operation Timer Turbo 24
℃
27
℃
×
×
◑
◑
◑
×
◑
◑
◑
●
◑
◑
◑
×
※ ●
: ON
◑
: Flash ×: OFF
Judgment
Method
• When the heating refrigerant charge : If the outdoor temperature is more than 15
℃
Cause of
problem
• System protection operation status (Is not breakdown)
4-3 Appropriate Measures for Different Symptom (cont.)