284
Key Options
8-2 List of Field Setting Items
No
Optional item
Purpose
00
Emergency operation for
compressor malfunction
To exclude the faulty compressor from the system. (emergency use only)
01
Cooling capacity correction
By this option system cooling capacity can be increased or decreased as evapo-
rator’s temperature will be colder or hotter than default.
02
Capacity correction for heating
By this option system heating capacity can be increased or decreased as evapo-
rator’s temperature will be colder or hotter than default.
03
Current restriction rate
To control the power consumption of the system for the building management
for peak control.
04
Oil collection interval
To shorten the Oil collection interval by 1/2 (Service use only)
05
Temperature to trigger defrost operation
To secure clean defrost in harsh condition.
06
Fan speed correction
Increase maximum fan rpm range to secure enough airflow when discharge
guide duct for outdoor unit is adapted.
07
Silent mode for night-time
Limit Maximum fan rpm & compressor frequency to reduce noise during the
night time → Max 15dB reduction.
* Only for cooling & Main cooling operation
08
High-head condition setting
To optimize the refrigerant control of the system according to the installation
condition.
09
Long-piping condition setting
To optimize the system control according to the installation condition.
10
Energy saving setting
To save energy in heating mode by controlling the target high pressure in heat-
ing.
11
Rotation defrost
Continuous heating operation during defrost in module installation.
(HR model only)
During the R-defrost Heating Indoor unit’s airflow will be set as low.
12
Expand operational temperature range
for cooling
To expand cooling operation range up to -15℃.
(HR model only, Default : -5℃)
13
Channel address
To recognize each outdoor system when using centralized controller.
14
Snow accumulation prevention
To prevent snow is accumulating on the outdoor unit fan discharge guide.
17
Speed operation
To increase cooling or heating speed.
18
Max. capacity restriction
Restrict excessive capacity increase when operating indoor units with small
capacity.
19
Gas leak Pump down
If the gas leak occurred it should be entered in the pump down operation.
Содержание AM072BXV Series
Страница 141: ...Troubleshooting Samsung Electronics 135 4 3 Appropriate Measures for Different Symptom cont...
Страница 160: ...Samsung Electronics 154 Troubleshooting 4 4 2 Pump down operation cont 4 4 Case study for trouble shoots cont...
Страница 162: ...Samsung Electronics 156 Troubleshooting 4 4 3 Pump out operation cont 4 4 Case study for trouble shoots cont...
Страница 190: ...PBA Diagram and Parts List Samsung Electronics 184 5 8 PF8 Inv Integration J POWER 1 2 3 4 5 6 1 7 8 12 11 10 9...
Страница 192: ...PBA Diagram and Parts List Samsung Electronics 186 5 9 PF8 Inv Integration F POWER 1 2 3 4 5 6 11 10 9 12 1 7 8...
Страница 200: ...Samsung Electronics 194 Wiring Diagram This Document can not be usedwithout Samsung s authorization 6 3 AM162BXVGF AA...
Страница 201: ...Samsung Electronics 195 Wiring Diagram 6 4 AM192BXVGJ AA This Document can not be usedwithout Samsung s authorization...