How to use inverter checker (Warning for high pressure)
►
Check between MOTOR
↔
FAN PBA
1) After cut off, connect inverter checker with U,V,W of Motor
2) After turn on, enter Comp. check mode by pushing K2 in main PBA
3) Judgment
•
6 LEDs of inverter checker are lightning successively (MOTOR PBA OK, MOTOR NG)
•
If one of 6 LEDs in inverter checker is not lightning (MOTOR PBA NG, MOTOR OK)
■
How to enter check mode/7Seg display
Type
DVM S
Model
Air Cooled
Water Cooled
COMP 1
9times (KD__)
8times (KD__)
COMP 2
10times (KE__)
9times (KE__)
MOTOR 1
11times (KF__)
MOTOR 2
12times (KG__)
Replace Compressor/Fan motor
PBA Defective
Power Off
( Use to inverter checker )
Replace Inverter PBA /Fan PBA
4-3-46 COMP Overcurrent error
4-3 Appropriate Measures for Different Symptom (cont.)
Содержание AM072BXV Series
Страница 141: ...Troubleshooting Samsung Electronics 135 4 3 Appropriate Measures for Different Symptom cont...
Страница 160: ...Samsung Electronics 154 Troubleshooting 4 4 2 Pump down operation cont 4 4 Case study for trouble shoots cont...
Страница 162: ...Samsung Electronics 156 Troubleshooting 4 4 3 Pump out operation cont 4 4 Case study for trouble shoots cont...
Страница 190: ...PBA Diagram and Parts List Samsung Electronics 184 5 8 PF8 Inv Integration J POWER 1 2 3 4 5 6 1 7 8 12 11 10 9...
Страница 192: ...PBA Diagram and Parts List Samsung Electronics 186 5 9 PF8 Inv Integration F POWER 1 2 3 4 5 6 11 10 9 12 1 7 8...
Страница 200: ...Samsung Electronics 194 Wiring Diagram This Document can not be usedwithout Samsung s authorization 6 3 AM162BXVGF AA...
Страница 201: ...Samsung Electronics 195 Wiring Diagram 6 4 AM192BXVGJ AA This Document can not be usedwithout Samsung s authorization...