Samsung Electronics
80
Troubleshooting
■
Initial Tracking (Communication Check-up)- Display
for Problem
1. For the display module of the outdoor unit, there are differences in the contents displayed depending on whether the relevant
outdoor unit is a master unit or a sub unit.
1) Master Unit
- The outdoor unit Micom attempts communication with the indoor unit connected to the communication cable (F1/F2) when
the power is turned on.
- Basic segment display
- If the number of indoor units set by the outdoor unit is not in accordance with the number of indoor units that succeeded with
communication, then the four displaying parts will display
.
2) Sub(Slave) Unit
-
The two left hand displays show its own address and the two right hand displays show the outdoor unit's address.
Main address : C8, Sub1 address : C9, Sub2 address : CA, Sub3 address : CB
g
SEG1
a f
G1
G2
b c e d
SEG2
g
SEG3
a f
G1
G2
b c e d
SEG4
Outdoor Unit Display Parts
Step
Display content
Display
At initial power input Checking segment
display
SEG1
SEG2
SEG3
SEG4
"8"
"8"
"8"
"8"
While setting
communication
between indoor and
outdoor unit
(Addressing)
Number of
connected
indoor units
SEG1
SEG2
SEG3, 4
SEG3, 4
"A"
"d"
Number of
communicated units
※ Refer to "View
Mode" for
communication
address
After communication
setting
(usual occasion)
Transmit/Reception
address
SEG1
SEG2
SEG3, 4
SEG3, 4
I/U : “A”
MCU : “C”
I/U : “0”
MCU : “1”
Reception address
(in decimal number)
※ I/U : Indoor unit
4-3 Appropriate Measures for Different Symptom
4-3-1 Outdoor Unit Test Operation Flow (cont.)
■
Quantity of indoor unit [Push Button Type]
Display
Description
•
Manual setting mode (Default).
- Press the K2 button shortly : Setting a 10-digit
- Press the K4 button shortly : Setting a 1-digit
• Automatic settings mode (Option)
Press and hold the K4 button : It is changed to the automatic setting mode,
and displays the number of the connected indoor unit.
(Ex. Of 10 indoor units are connected, "id 10" is indicated.)
- If press the K2, K4 button shortly in the automatic setting mode, it is changed to the manual
mode. (Ex. If 10 is indicated and press the K4 button, 11 is indicated and changed to the manual
mode.)
Содержание AM072BXV Series
Страница 141: ...Troubleshooting Samsung Electronics 135 4 3 Appropriate Measures for Different Symptom cont...
Страница 160: ...Samsung Electronics 154 Troubleshooting 4 4 2 Pump down operation cont 4 4 Case study for trouble shoots cont...
Страница 162: ...Samsung Electronics 156 Troubleshooting 4 4 3 Pump out operation cont 4 4 Case study for trouble shoots cont...
Страница 190: ...PBA Diagram and Parts List Samsung Electronics 184 5 8 PF8 Inv Integration J POWER 1 2 3 4 5 6 1 7 8 12 11 10 9...
Страница 192: ...PBA Diagram and Parts List Samsung Electronics 186 5 9 PF8 Inv Integration F POWER 1 2 3 4 5 6 11 10 9 12 1 7 8...
Страница 200: ...Samsung Electronics 194 Wiring Diagram This Document can not be usedwithout Samsung s authorization 6 3 AM162BXVGF AA...
Страница 201: ...Samsung Electronics 195 Wiring Diagram 6 4 AM192BXVGJ AA This Document can not be usedwithout Samsung s authorization...