Disassembly and Reassembly
Samsung Electronics
49
3-2 Disassembly and Reassembly (cont.)
STEP
Occasion that compressor is 1 inside outdoor unit
Occasion that compressor is 2 inside outdoor unit
1
Set the compressor to be replaced by cutting
2
-
Refrigerant release driving of applied outdoor unit
※ Refrigerant release driving enforces 1th necessarily.
Release driving that enforce contiguously can be
responsible for compressor breakdown.
3
Lock all SVC valve of liquid pipe and gas pipe.
4
Enter in vacuum mode and establish as all EEV and Valve open.
5
Reclaim refrigerant of outdoor unit using Recovery Unit.
※ When there is no Recovery Unit, refer to below contents.
1. If refrigerant release driving is enforced, refrigerant remaining amount of outdoor unit inside is about 1.5kg ordinarily.
Temperature can remain more refrigerant because refrigerant fills to Accumulator in the winter day.
2. Refer to factory charging refrigerant had registered to Label of outdoor unit.
3. Can get help that decide an addition refrigerant quantity if use refrigerant quantity decision function that use
S-Checker.
6
Turn off the power linked by outdoor unit.
7
Separate compressor that broke down from outdoor unit.
※ Confirm through manifold gauge whether refrigerant of outdoor unit was reclaimed all necessarily before use welding
machine for replace of compressor.
8
Measure quantity of broke down oil of compressor.
9
Confirm state and color of compressor oil that broke down.
10
-
When is judged that oil was polluted, compressor beside
(ASTM : more than 3) measures quantity of replace and oil.
11
Decide quantity of oil to pour in addition according to sheep of changing oil of compressors.
12
Change by new compressor.
Add oil according to sheep of oil that pour decided addition before.
13
Establish again by vacuum mode after connect power.
14
Execute leakage examination using nitrogen
vacuum work
15
Add a refrigerant quantity deciding from step 5.
16
Execute Auto Trial Operation after open SVC Valve.
3-2-7 Compressor exchange order
Содержание AM072BXV Series
Страница 141: ...Troubleshooting Samsung Electronics 135 4 3 Appropriate Measures for Different Symptom cont...
Страница 160: ...Samsung Electronics 154 Troubleshooting 4 4 2 Pump down operation cont 4 4 Case study for trouble shoots cont...
Страница 162: ...Samsung Electronics 156 Troubleshooting 4 4 3 Pump out operation cont 4 4 Case study for trouble shoots cont...
Страница 190: ...PBA Diagram and Parts List Samsung Electronics 184 5 8 PF8 Inv Integration J POWER 1 2 3 4 5 6 1 7 8 12 11 10 9...
Страница 192: ...PBA Diagram and Parts List Samsung Electronics 186 5 9 PF8 Inv Integration F POWER 1 2 3 4 5 6 11 10 9 12 1 7 8...
Страница 200: ...Samsung Electronics 194 Wiring Diagram This Document can not be usedwithout Samsung s authorization 6 3 AM162BXVGF AA...
Страница 201: ...Samsung Electronics 195 Wiring Diagram 6 4 AM192BXVGJ AA This Document can not be usedwithout Samsung s authorization...