Samsung Electronics
230
Piping Diagram
Solenoid Valve – Main EEV
▪
Purpose
In main cooling mode, enable the Main EEV to control the amount of refrigerant flowing in the cooling indoor units.
▪
Concept
-
In main cooling mode, the valve is closed to prevent refrigerant from flowing using Check Valve.
- EEV Bypass and enable the Main EEV to control the amount of refrigerant flowing into the cooling indoor units.
- If the valve is opened, most refrigerant is bypassed via the valve which flows into the cooling indoor units.
As a result, there is insufficient refrigerant in active indoor units that are under heating mode.
- HR Only
▪
Control specifications in detail
In main cooling mode, the valve is Off (closed).
Solenoid Valve – Main Cooling
▪
Purpose
In main cooling mode, enable operation of heating indoor units.
▪
Concept
-
In main cooling mode, the valve is opened to send the high pressure to heating indoor units and enable heating.
- HR Only
▪
Control specifications in detail
In main cooling mode, the valve is On (opened)
7-3 Functions (cont.)
7-3-2-1 Actuator (cont.)
7-3-2 Control (cont.)
Solenoid Valve - Accumulator Oil Return (ARV)
▪
Purpose
Return oil stagnating in the accumulator.
▪
Concept
-
During compressor operation, the valve is opened to return oil stagnating in the accumulator.
-
The valve is closed to protect the compressor in start-up mode or in a section where there is concern about the potential for liquid
compression due to low DSH.
▪
Control specifications in detail
-
Condition(s) required to close (Off) the valve : [ A or B or C ]
A. The system has stopped
B. DSH is higher than 10 K during start-up
C. The valve is closed for 2 minutes if DSH is higher than 10 K in air conditioning mode.
- Condition(s) required to open (On) the valve : None of the conditions required to close the valve are satisfied.
Compressor Coil Heater (CCH)
▪
Purpose
Prevent compressor failure due to liquid compression or poor lubrication during compressor start-up.
▪
Concept
If the internal temperature of an inactive compressor is abnormally low, the internal temperature is increased through the CCH to evap
-
orate the liquid refrigerant that has flowed into the compressor. This will prevent liquid compression and poor lubrication.
▪
Control specifications in detail
-
It is turned On if A or B is satisfied.
A. The highest temperature of the compressor has remained below 50
℃
for 2 min.
B. The CCH has been Off for longer than 6 hours.
- Condition(s) required to turn Off the CCH: [ A or B ]
A. The highest temperature of the compressor has remained above 55
℃
for 30 min.
B. The CCH has been On for longer than 6 hours.
Содержание AM072BXV Series
Страница 141: ...Troubleshooting Samsung Electronics 135 4 3 Appropriate Measures for Different Symptom cont...
Страница 160: ...Samsung Electronics 154 Troubleshooting 4 4 2 Pump down operation cont 4 4 Case study for trouble shoots cont...
Страница 162: ...Samsung Electronics 156 Troubleshooting 4 4 3 Pump out operation cont 4 4 Case study for trouble shoots cont...
Страница 190: ...PBA Diagram and Parts List Samsung Electronics 184 5 8 PF8 Inv Integration J POWER 1 2 3 4 5 6 1 7 8 12 11 10 9...
Страница 192: ...PBA Diagram and Parts List Samsung Electronics 186 5 9 PF8 Inv Integration F POWER 1 2 3 4 5 6 11 10 9 12 1 7 8...
Страница 200: ...Samsung Electronics 194 Wiring Diagram This Document can not be usedwithout Samsung s authorization 6 3 AM162BXVGF AA...
Страница 201: ...Samsung Electronics 195 Wiring Diagram 6 4 AM192BXVGJ AA This Document can not be usedwithout Samsung s authorization...