Piping Diagram
Samsung Electronics
281
Rotation defrost
▪
Purpose
Enable continuous heating when HR modules are used.
▪
Concept
- Continuous heating is provided by performing defrost operation for each unit if HR modules are used.
- HR Only
▪
Control specifications in detail
- In heating mode, defrost operation is performed on each unit one after another according to the order of rotation priority.
(see "Rotation defrost control" for details).
Input unit
Seg1
Seg2
Seg3
Seg4
Rotation defrost
Main
1
1
0
0
Disabled (default)
0
1
Enabled
▪
Notes
- Incorrect settings may seriously damage the system.
- Setting is unnecessary if high-head condition is set.
Expand operational temperature range for cooling
▪
Purpose
Extend the low temperature operation range for HR units to -15℃ .
▪
Concept
- The cooling operation range is extended by controlling purpose-specific valves on HR units.
- HR Only
▪
Control specifications in detail
- If it is difficult to secure outdoor high pressure while in cooling mode in an outdoor location with a low temperature,
formation of high pressure is facilitated by controlling the low pressure decrease, Solenoid valve.
- Main EEV, and Solenoid valve.
- Hot gas bypass.
Input unit
Seg1
Seg2
Seg3
Seg4
Expand operational temperature range for
cooling operation (HR only)
Main
1
2
0
0
Disabled (default)
0
1
Enabled
▪
Notes
- Continuous cooling operation is possible even in low temperature condition up to -15℃ , but noise of the MCU will
increase.
- This option is only for HR unit.
Channel address
▪
Purpose
- Identify multiple main outdoor units connected to upper-level controllers, such as DMS and S-NET3.
▪
Concept
- If the Channel address is set, the same channel address is assigned to the sub outdoor units, indoor units,
and MCUs connected to a main outdoor unit.
▪
Control specifications in detail
Input unit
Seg1
Seg2
Seg3
Seg4
Channel address
Main
1
3
A
U
Automatic setting (default)
0~15
Manual setting for channel
0 - 15
7-3 Functions (cont.)
7-3-3-1 Field Setting (cont.)
7-3-3 Others (cont.)
Содержание AM072BXV Series
Страница 141: ...Troubleshooting Samsung Electronics 135 4 3 Appropriate Measures for Different Symptom cont...
Страница 160: ...Samsung Electronics 154 Troubleshooting 4 4 2 Pump down operation cont 4 4 Case study for trouble shoots cont...
Страница 162: ...Samsung Electronics 156 Troubleshooting 4 4 3 Pump out operation cont 4 4 Case study for trouble shoots cont...
Страница 190: ...PBA Diagram and Parts List Samsung Electronics 184 5 8 PF8 Inv Integration J POWER 1 2 3 4 5 6 1 7 8 12 11 10 9...
Страница 192: ...PBA Diagram and Parts List Samsung Electronics 186 5 9 PF8 Inv Integration F POWER 1 2 3 4 5 6 11 10 9 12 1 7 8...
Страница 200: ...Samsung Electronics 194 Wiring Diagram This Document can not be usedwithout Samsung s authorization 6 3 AM162BXVGF AA...
Страница 201: ...Samsung Electronics 195 Wiring Diagram 6 4 AM192BXVGJ AA This Document can not be usedwithout Samsung s authorization...