Resolution on output frequency ............................................................................................................. ±0.003 Hz
System response time ............................................................................................................................... 3 msec.
Speed, control range (open loop) .................................................................................... 1:100 of synchro. speed
Speed, accuracy (open loop) ........................................................................... < 1500 rpm:max. error ± 7.5 rpm
> 1500 rpm: max. error of 0.5% of actual speed
Process, accuracy (closed loop) ....................................................................... < 1500 rpm: max.error ± 1.5 rpm
> 1500 rpm: max. error of 0.1% of actual speed
All control characteristics are based on a 4-pole asynchronous motor
Accuracy of display readout (parameters 009-012
Display readout
):
Motor current, 0 - 140% load ............................................................... Max. error: ±2.0% of rated output current
Power kW, Power HP, 0 - 90% load ..................................................... Max. error: ±5.0% of rated output power
Externals:
Enclosure .................................................................................. IP00/Chassis, IP20/IP21/NEMA 1, IP54/NEMA 12
Vibration test ................................ 0.7 g RMS 18-1000 Hz random. 3 directions for 2 hours (IEC 68-2-34/35/36)
Max. relative humidity ............................................................ 93 % +2 %, -3 % (IEC 68-2-3) for storage/transport
Max. relative humidity .............................................. 95% non condensing (IEC 721-3-3; class 3K3) for operation
Aggressive environment (IEC 721-3-3) .................................................................................... Uncoated class 3C2
Aggressive environment (IEC 721-3-3) ....................................................................................... Coated class 3C3
Ambient temperature, VLT 8006-8011 380-480 V, 8002-8011 525-600 V, IP 20//NEMA 1 ...................................
Max. 45°C (117°F) (24-hour average max. 40°C (104°F))
Ambient temperature IP00/Chassis, IP20/NEMA 1, IP54/NEMA 12, VLT 8011 480 V ................................... Max.
40°C/104°F (24-hour average max.
35°C/95°F)
see Derating for high ambient temperature
Min. ambient temperature in full operation ............................................................................................ 0°C (32°F)
Min. ambient temperature at reduced performance .......................................................................... -10°C (14°F)
Temperature during storage/transport ....................................................... -25° - +65°/70°C (-13° - +149°/158°F)
Max. altitude above sea level ...................................................................................................... 1000 m (3300 ft)
see Derating for high air pressure
NOTE
VLT 8002-8300, 525-600 V units do not comply
with EMC, Low Voltage or PELV directives.
VLT 8000 AQUA protection:
•
Electronic motor thermal protection against overload.
•
Temperature monitoring of heatsink ensures that the adjustable frequency drive cuts out if the
temperature reaches 90° C (194° F) for IP00/Chassis and IP20/NEMA 1. For IP54/NEMA 12, the
cut-out temperature is 80° C (176° F). An overtemperature can only be reset when the temperature
of the heatsink has fallen below 60° C (140° F).
For the units mentioned below, the limits are as follows:
- VLT 8151-8202, 380-480 V cuts out at 80° C (176° F) and can be reset if the temperature is below
60 °C (140° F).
- VLT 8252-8352, 380-480 V cuts out at 105 °C (221° F) and can be reset if the temperature has
fallen below 70° C (158° F).