VLT
®
8000 AQUA
Introduction
■
LC filters VLT 8006-8011 380 - 480 V
The drawing on the left gives the measurements of IP
20 LC filters for the above-mentioned power range.
Min. space above and under enclosure: 100 mm.
IP 20 LC filters have been designed for side-by-side
installation without any space between enclosures.
Max. motor cable length:
-
150 m shielded/armored cable
-
300 m unshielded/unarmored cable
If EMC standards are to be complied with:
EN 55011-1B: Max. 50 shielded/armored cable
Bookstyle: Max. 20 m shielded/armored cable
EN 55011-1A: Max. 150 m shielded/armored
cable
Weight:
175Z0832
9.5 kg
■
Installation of LC filter IP 20
MG.80.A7.22 - VLT is a registered Danfoss trademark
19
Rosewood STP ST42 General (Operation and Maintenance Manual - Part 4:
Section 6.3 Manufacturers Manuals 6.3.33 Danfoss VLT Aquadrive 8000) Vendor Manual
QP Id: VM207
Active: 03/09/2013