VLT
®
8000 AQUA
Installation
■
Technical data, line supply 3 x 380 - 480 V
According to international requirements
VLT type
8052
8062
8072
8102
8122
Output current
I
VLT,N
[A] (380-440 V)
73.0
90.0
106
147
177
I
VLT, MAX
(60 s) [A]
(380-440 V)
80.3
99.0
117
162
195
I
VLT,N
[A] (441-480 V)
65.0
77.0
106
130
160
I
VLT, MAX
(60 s) [A]
(441-480 V)
71.5
84.7
117
143
176
Output power
S
VLT,N
[kVA] (400 V)
52.5
64.7
73.4
102
123
S
VLT,N
[kVA] (460 V)
51.8
61.3
84.5
104
127
Typical shaft output
P
VLT,N
[kW]
37
45
55
75
90
Typical shaft output
P
VLT,N
[HP]
50
60
75
100
125
Max.
cable
cross-section to motor
and DC-bus, IP 20
35/2
50/0
50/0
120
/ 250
mcm
5)
120
/ 250
mcm
5)
Max.
cable
cross-section to motor
and DC-bus, IP 54
[mm
2
]/[AWG]
2) 4) 6)
35/2
50/0
50/0
150
/ 300
mcm
5)
150
/ 300
mcm
5)
Min. cable cross-section
to motor and DC-bus
[mm
2
]/[AWG]
2) 4)
10/8
16/6
16/6
25/4
25/4
Max. input current
I
L,N
[A] (380 V)
72.0
89.0
104
145
174
(RMS)
I
L,N
[A] (480 V)
64.0
77.0
104
128
158
Max.
cable
cross-section power,
IP 20
35/2
50/0
50/0
120
/ 250
mcm
120
/ 250
mcm
Max.
cable
cross-section power,
IP 54
[mm
2
]/[AWG]
2) 4) 6)
35/2
50/0
50/0
150
/ 300
mcm
150
/ 300
mcm
Max. pre-fuses
[-]/UL
1)
[A]
100/100
125/125 150/150 225/225 250/250
AC line contactor
[Danfoss type]
CI 37
CI 61
CI 85
CI 85
CI 141
Efficiency at rated frequency
0.96
0.96
0.96
0.98
0.98
Weight IP 20/NEMA 1
[kg/lbs]
41/90
42/93
43/96
54/119
54/119
Weight IP 54/NEMA 12
[kg/lbs]
56/123
56/123
60/132
77/170
77/170
Power loss at max. load.
[W]
1275
1571
1322
<1467
<1766
Enclosure
IP 20/NEMA 1/IP 54/NEMA 12
1. For type of fuse, see section
Fuses
.
2. American Wire Gauge.
3. Measured using 30 m/100 ft shielded motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals.
Max. cable cross-section is the maximum possible cable cross-section that can be fitted on the
terminals.
Always comply with national and local regulations on min. cable cross-section.
5. DC connection 95 mm
2
/AWG 3/0.
6. Aluminum cables with cross-section more than 35 mm
2
/2 AWG must be connected by use of an
Al-Cu connector.
MG.80.A7.22 - VLT is a registered Danfoss trademark
37
Rosewood STP ST42 General (Operation and Maintenance Manual - Part 4:
Section 6.3 Manufacturers Manuals 6.3.33 Danfoss VLT Aquadrive 8000) Vendor Manual
QP Id: VM207