VLT
®
8000 AQUA
Description of choice:
The dimension of this parameter is Units/Second. The
Units will be the value selected in parameter 415.
As an example, the Units could be Bar, or MPa, or
PSI, etc. If Bar is the selected unit in parameter 415,
then the number set in this parameter (230) would
be dimensioned as Bar/Second. Changes to this
parameter can be made in steps of .001 units.
231 Filled Setpoint
(FILLED SETPOINT)
Value:
Param. 413 - Param. 205 -
✭
Param.
413
Function:
The value set in this parameter corresponds
to the pressure that exists at the pressure
sensor when the pipe is filled.
Description of choice:
The Units of this parameter correspond to the units
selected in Parameter 415. The minimum value of
this parameter is Fb
min
(param. 413). The maximum
value for this parameter is Ref
max
(param. 205). The
setpoint can be changed in .01 steps.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.80.A7.22 - VLT is a registered Danfoss trademark
112