Description of choice:
In some cases this dynamic compensation can cause
resonance
’
s in the DC link and should then be disabled.
Typical cases are where a line choke or a passive
harmonic filter (e.g. filters AHF005/010) is mounted
in the line supply to the AFD to suppress harmonics.
Can also occur on line with low short circuit ratio.
NOTE
This is a hidden parameter. The only access
is with the MCT 10 software tool.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port