VLT
®
8000 AQUA
0-f
MAX
⇒
0-32000 p
, which generates an output signal
proportional to the output frequency in the interval 0 -
f
MAX
(parameter 202
Output frequency, high limit, f
MAX
).
External Ref
MIN
- Ref
MAX
⇒
0-20 mA
and
External Ref
MIN
- Ref
MAX
⇒
4-20 mA
and
External Ref
MIN
- Ref
MAX
⇒
0-32000 p
which
generates an output signal proportional to the
resulting reference value in the interval
Minimum
reference, Ref
MIN
- Maximum reference, Ref
MAX
(parameters 204/205).
FB
MIN
-FB
MAX
⇒
0-20 mA
and
FB
MIN
-FB
MAX
⇒
4-20mA
and
FB
MIN
-FB
MAX
⇒
0-32000 p
an output signal
proportional to the reference value in the interval
Minimum feedback, FB
MIN
- Maximum feedback,
FB
MAX
(parameters 413/414) is obtained.
0 - I
VLT,MAX
⇒
0-20 mA
and
0 - I
VLT,MAX
⇒
4-20 mA
and
0 - I
VLT,MAX
⇒
0-32000 p
, an output signal
proportional to the output current in the interval
0 - I
VLT,MAX
is obtained.
0 - p
NOM
⇒
0-20 mA
and
0 - p
NOM
⇒
4-20 mA
and
0 - p
NOM
⇒
0-32000 p
, which generates an
output signal proportional to the present output
power. 20 mA corresponds to the value set in
parameter 102
Motor power, P
M,N
.
0.0 - 100.0%
⇒
0 - 20 mA
and
0.0 - 100.0%
⇒
4 - 20 mA
and
0.0 - 100.0%
⇒
0 - 32.000
pulses which generates an
output signal proportional to the value (0.0-100.0%)
received by serial communication. Writing from Serial
communication is done to parameter 364 (terminal
42) and 365 (terminal 45). This function is limited to
the following protocols: FC bus, Profibus, LonWorks
FTP, DeviceNet, and Modbus RTU.
Motor alternation
A relay or digital output can be
used in conjunction with output contactors to alternate
the AFD
’
s output between motors based on an
internal timer. See parameters 433 and 434 for further
information and programming information.
320 Terminal 42, output, pulse scaling
(AO 42 PULS SCALE)
Value:
1 - 32000 Hz
✭
5000 Hz
Function:
This parameter allows scaling of the pulse output signal.
Description of choice:
Set the desired value.
321 Terminal 45, output
(AO 45 FUNCTION)
Value:
See description of parameter 319
Terminal
42, Output.
Function:
This output can function both as a digital or an analog
output. When used as a digital output (data value
[0]-[26]) it generates a 24 V (max. 40 mA) signal. For
the analog outputs (data value [27] - [41]) there is a
choice of 0-20 mA, 4-20 mA or a pulse sequence.
Description of choice:
See description of parameter 319
Terminal 42, Output.
322 Terminal 45, output, pulse scaling
(AO 45 PULS SCALE)
Value:
1 - 32000 Hz
✭
5000 Hz
Function:
This parameter allows scaling of the pulse output signal.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.80.A7.22 - VLT is a registered Danfoss trademark
122
Rosewood STP ST42 General (Operation and Maintenance Manual - Part 4:
Section 6.3 Manufacturers Manuals 6.3.33 Danfoss VLT Aquadrive 8000) Vendor Manual
QP Id: VM207
Active: 03/09/2013
Page 128 of 208