VLT
®
8000 AQUA
Programming
[10]
Setpoint 1 [unit] (SETPOINT 1 [UNITS])
[11]
Setpoint 2 [unit] (SETPOINT 2 [UNITS])
[12]
Feedback 1 (FEEDBACK 1 [UNITS])
[13]
Feedback 2 (FEEDBACK 2 [UNITS])
[14]
Feedback [unit] (FEEDBACK [UNITS])
[15]
Motor voltage [V] (MOTOR VOLTAGE [V])
[16]
DC link voltage [V] (DC VOLTAGE [V])
[17]
Thermal load, motor [%]
(THERM.MOTOR LOAD [%])
[18]
Thermal load, VLT [%]
(THERM.DRIVE LOAD [%])
[19]
Digital input [Binary code]
(DIGITAL INPUT [BIN])
[20]
Analogue input 53 [V] (ANALOG INPUT 53 [V])
[21]
Analogue input 54 [V] (ANALOG INPUT 54 [V])
[22]
Analogue input 60 [mA]
(ANALOG INPUT 60 [MA])
[23]
Relay status [binary code] (RELAY STATUS)
[24]
Pulse reference [Hz] (PULSE REFERENCE [HZ])
[25]
External reference [%] (EXT. REFERENCE [%])
[26]
Heat sink temp. [°C] (HEATSINK TEMP [°C])
[27]
Communication option card warning
(COMM OPT WARN [HEX])
[28]
LCP display text (FREE PROG.ARRAY)
[29]
Status word (STATUS WORD [HEX])
[30]
Control word (CONTROL WORD [HEX])
[31]
Alarm word (ALARM WORD [HEX])
[32]
PID output [Hz] (PID OUTPUT [HZ])
[33]
PID output [%] (PID OUTPUT [%])
[34]
Function:
This parameter allows a choice of the data value
to be shown in the display, line 2, when the AFD
is turned on. The data values will also be included
in the display mode scroll-list. Parameters 008-010
Small display readout
allow a choice of another
three data values, shown in line 1.
See the description of the
control unit.
Description of choice:
No readout
can only be selected in parameters
008-010
Small display readout
.
Resulting reference [%]
gives a percentage for
the resulting reference in the range from
Minimum
reference
, Ref
MIN
to Maximum reference, Ref
MAX
. See also
reference handling
.
Reference [unit]
gives the resulting reference in Hz
in
Open loop
. In
Closed loop
, the reference unit is
selected in parameter 415
Process units
.
Frequency [Hz]
gives the output frequency
from the AFD.
% of maximum output frequency [%]
is the present
output frequency as a percentage value of parameter
202
Output frequency high limit, f
MAX
.
Motor current [A]
states the phase current of
the motor measured as effective value.
Power [kW]
states the actual power consumed
by the motor in kW.
Power [HP]
states the actual power consumed
by the motor in HP.
Output energy [kWh]
states the energy consumed
by the motor since the latest reset was made in
pa-rameter 618
Reset of kWh
counter.
Hours run [Hours]
states the number of hours
that the motor has run since the latest reset in
parameter 619
Reset of hours-run counter
.
User -defined readout [-]
is a user-defined value,
calculated on the basis of the present output frequency
and unit, as well as the scaling in parameter 005
Max. value of user-defined readout.
Select unit in
parameter 006
Unit for user-defined readout.
Setpoint 1 [unit]
is the programmed setpoint
value in parameter 418
Setpoint 1
. The unit
is decided in parameter 415
Process units
.
See also
Feedback handling
.
Setpoint 2 [unit]
is the programmed setpoint value
in parameter 419
Setpoint 2
. The unit is decided
in parameter 415
Process units
.
Feedback 1 [unit]
gives the signal value of the
resulting feedback 1 (Term. 53). The unit is
decided in parameter 415
Process units
. See
also
Feedback handling
.
Feedback 2 [unit]
gives the signal value of the
resulting feedback 2 (Term. 53). The unit is decided
in parameter 415
Process units
.
Feedback [unit]
gives the resulting signal value
using the unit/scaling selected in parameter 413
Minimum feedback
, FB
MIN
, 414
Maximum feedback
,
FB
MAX
and 415
Process units
.
Motor voltage [V]
states the voltage supplied
to the motor.
DC link voltage [V]
states the intermediate
circuit voltage in the AFD.
Thermal load, motor [%]
states the calculated/
estimated thermal load on the motor. 100%
is the cut-out limit. See also parameter 117
Motor thermal protection
.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.80.A7.22 - VLT is a registered Danfoss trademark
89
Rosewood STP ST42 General (Operation and Maintenance Manual - Part 4:
Section 6.3 Manufacturers Manuals 6.3.33 Danfoss VLT Aquadrive 8000) Vendor Manual
QP Id: VM207
Active: 03/09/2013
Page 95 of 208