VLT
®
8000 AQUA
All about VLT 8000
AQUA
Freeze output request (FRZ.REQ.)
A freeze output command has been given, but the
motor will remain stopped until a Run permissive
signal is received via a digital input.
Reversing and start (START F/R)
Reversing and start
[2] on terminal 19 (parameter
303
Digital inputs
) and
Start
[1] on terminal 18
(parameter 302
Digital inputs
) are enabled at the
same time. The motor will remain stopped until
one of the signals becomes a logic ‘0
’
.
Automatic Motor Adaptation running (AMA RUN)
Automatic motor adaptation has been enabled in
parameter 107
Automatic Motor Adaptation, AMA.
Automatic Motor Adaptation completed
(AMA STOP)
Automatic motor adaptation has ben completed. The
AFD is now ready for operation after the
Reset
signal
has been enabled. Please note that the motor will
start after the AFD has received the
Reset
signal.
Stand by (STANDBY)
The AFD is able to start the motor when a
start command is received.
Stop (STOP)
The motor has been stopped via a stop signal
from a digital input, [OFF/STOP]-buttom or
serial communication.
DC stop (DC STOP)
The DC brake in parameter 114-116 has been enabled.
DRIVE ready (UN. READY)
The AFD is ready for operation, but terminal 27 is
a logic "0" and/or a
Coasting command
has been
received via the serial communication.
Not ready (NOT READY)
The AFD is not ready for operation, because of a trip
or because OFF1, OFF2 or OFF3 is a logic ‘0
’
.
Start disabled (START IN.)
This status will only be displayed if, in parameter
599
Statemachine, Profidrive
[1] has been selected
and OFF2 or OFF3 is a logic ‘0
’
.
Exceptions XXXX (EXCEPTIONS XXXX)
The microprocessor of the control card has stopped
and the AFD is out of operation.
The cause may be noise on the line, motor
or control cables, leading to a stop of the
control card microprocessor.
Check for EMC-correct connection of these cables.
MG.80.A7.22 - VLT is a registered Danfoss trademark
171
Rosewood STP ST42 General (Operation and Maintenance Manual - Part 4:
Section 6.3 Manufacturers Manuals 6.3.33 Danfoss VLT Aquadrive 8000) Vendor Manual
QP Id: VM207
Active: 03/09/2013
Page 177 of 208