VLT
®
8000 AQUA
■
Factory settings
PNU
#
Parameter
description
Factory setting
Range
Changes
during
operation
4-setup
Conver-
sion
index
Data
type
300
Terminal 16 Digital input
Reset
Yes
Yes
0
5
301
Terminal 17 Digital input
No operation
Yes
Yes
0
5
302
Terminal 18 Digital input
Start
Yes
Yes
0
5
303
Terminal 19 Digital input
Reversing
Yes
Yes
0
5
304
Terminal 27 Digital input
Safety interlock/
Coasting stop,
inverse
Yes
Yes
0
5
305
Terminal 29 Digital input
Jog
Yes
Yes
0
5
306
Terminal 32 Digital input
No operation
Yes
Yes
0
5
307
Terminal 33 Digital input
No operation
Yes
Yes
0
5
308
Terminal 53, analog input voltage
No operation
Yes
Yes
0
5
309
Terminal 53, min. scaling
0.0 V
0.0 - 10.0 V
Yes
Yes
-1
5
310
Terminal 53, max. scaling
10.0 V
0.0 - 10.0 V
Yes
Yes
-1
5
311
Terminal 54, analog input voltage
No operation
Yes
Yes
0
5
312
Terminal 54, min. scaling
0.0 V
0.0 - 10.0 V
Yes
Yes
-1
5
313
Terminal 54, max. scaling
10.0 V
0.0 - 10.0 V
Yes
Yes
-1
5
314
Terminal 60, analog input voltage
Reference
Yes
Yes
0
5
315
Terminal 60, min. scaling
4.0 mA
0.0 - 20.0 mA
Yes
Yes
-4
5
316
Terminal 60, max. scaling
20.0 mA
0.0 - 20.0 mA
Yes
Yes
-4
5
317
Time out
10 sec.
1 - 99 sec.
Yes
Yes
0
5
318
Function after time out
Off
Yes
Yes
0
5
319
Terminal 42, output
0 - I
MAX
⇒
4-20 mA
Yes
Yes
0
5
320
Terminal 42, output
pulse scaling
Yes
Yes
0
6
321
Terminal 42, output
0 - f
MAX
⇒
0-20 mA
Yes
Yes
0
5
322
Terminal 45, output,
Yes
Yes
pulse scaling
5000 Hz
1 - 32000 Hz
Yes
Yes
0
6
323
Relay 1, output function
No alarm
Yes
Yes
0
5
324
Relay 01, ON delay
0.00 sec.
0 - 600 sec.
Yes
Yes
0
6
325
Relay 01, OFF delay
2.00 sec.
0 - 600 sec.
Yes
Yes
0
6
326
Relay 2, output function
Running
Yes
Yes
0
5
327
Pulse reference,
max frequency
5000 Hz
Depends on
input terminal
Yes
Yes
0
6
328
Pulse feedback, max. frequency
25000 Hz
0 - 65000 Hz
Yes
Yes
0
6
364
Terminal 42, bus control
0
0.0 - 100 %
Yes
Yes
-1
6
365
Terminal 45, bus control
0
0.0 - 100 %
Yes
Yes
-1
6
) Coasting stop, inverse is global factory setting different from North American factory setting.
Changes during operation:
"Yes" means that the parameter can be changed,
while the AFD is in operation. "No" means that the
AFD must be stopped before a change can be made.
4-Setup:
"Yes" means that the parameter can be programmed
individually in each of the four setups, i.e. the
same parameter can have four different data
values. "No" means that the data value will
be the same in all four setups.
MG.80.A7.22 - VLT is a registered Danfoss trademark
194
Rosewood STP ST42 General (Operation and Maintenance Manual - Part 4:
Section 6.3 Manufacturers Manuals 6.3.33 Danfoss VLT Aquadrive 8000) Vendor Manual
QP Id: VM207
Active: 03/09/2013
Page 200 of 208