Power [HP], parameter 516:
Gives the present power absorption of the motor in HP.
Motor voltage, parameter 517:
Gives the voltage fed to the motor.
DC link voltage, parameter 518:
Gives the intermediate circuit voltage of the AFD.
Thermal load, motor [%], parameter 519:
Gives the calculated/estimated thermal load on
the motor. 100 % is the cut-out limit. See also
parameter 117
Motor thermal protection.
Thermal protection, VLT [%], parameter 520:
Gives the calculated/estimated thermal load on
the AFD. 100 % is the cut-out limit.
Digital input, parameter 521:
Gives the signal status of the 8 inputs (16, 17, 18,
19, 27, 29, 32 and 33). Input 16 corresponds
to the bit to the extreme left.
’
0
’
= no signal,
’
1
’
= signal connected.
Terminal 53, analogue input [V], parameter 522:
Gives the voltage value of the signal on terminal 53.
Terminal 54, analogue input [V], parameter 523:
Gives the voltage value of the signal on terminal 54.
Terminal erminal 60, analogue input [mA],
parameter 524:
Gives the current value of the signal on terminal 60.
Pulse reference [Hz], parameter 525:
Gives a pulse frequency in Hz connected to one
of the terminals 17 and 29.
External reference, parameter 526:
Gives the sum of external references as a percentage
(sum of analog/pulse/serial communication) in
the range from
Minimum reference, Ref
MIN
to
Maximum reference, Ref
MAX
.
Status word, parameter 527:
Gives the present status word of the AFD in Hex.
Heat sink temperature, parameter 528:
Gives the present heat sink temperature of the AFD.
The cut-out limit is 90 ± 5 °C/9 °F, while cutting
back in is effected at 60 ± 5 °C/9 °F.
Alarm word, parameter 529:
Gives a Hex code for the alarm on the AFD.
See
Warning words 1+2 and Alarm word
.
Control word, parameter 530:
Gives the present control word of the AFD in Hex.
Warning word, parameter 531:
Indicates in Hex whether there is a warning on the
AFD. See
Warning words 1+2 and Alarm word.
Extended status word, parameter 532:
Indicates in Hex code whether there is a warning on
the AFD. See
Warning words 1+2 and Alarm word.
Relay status, parameter 537:
Indicates in binary code whether the output relays
of the AFD are triggered or not.
533 Display text 1
(DISPLAY TEXT ARRAY 1)
Value:
Max.
20 characters
[XXXXXXXXXXXXXXXXXXXX]
Function:
Here, a text of max. 20 characters can be written
that will be shown in display line 1, provided
LCP
display text
[27] has been selected in parameter 007
Large display read-ou
t. Example of display text.
175ZA792.10
VLT NO.8
SETUP
1
CLEANING SYSTEM NO.2
AUTO REMOTE RUNNING
Description of choice:
Write the required text via serial communication.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.80.A7.22 - VLT is a registered Danfoss trademark
158
Rosewood STP ST42 General (Operation and Maintenance Manual - Part 4:
Section 6.3 Manufacturers Manuals 6.3.33 Danfoss VLT Aquadrive 8000) Vendor Manual