EMC test results (Emission, Immunity)
The following test results have been obtained using a system with an AFD (with options if relevant), a shielded control cable, a control box with potentiometer, as well as a motor and motor cable.
Emission
Environment
Industrial environment
Housing, trades and light industries
VLT 8006- 8011/ 380- 480V
Basic standard
EN 55011 Class A1
EN 55011 Class B
EN 61800- 3
Setup
Motor cable
Conducted 150 kHz-
30 MHz
Radiated 30 MHz- 1 GHz
Conducted 150 kHz-
30 MHz
Radiated 30 MHz- 1 GHz
Conducted/ radiated 150
kHz- 30 MHz
300 m unshielded/ unarmored
Yes
2)
No
No
No
Yes/ No
50 m br. shielded/ armored
(Bookstyle 20m )
Yes
Yes
Yes
4)
No
Yes/ Yes
VLT 8000 with RFI filter option
150m br. shielded/ armored
Yes
Yes
No
No
Yes/ Yes
300 m unshielded/ unarmored
Yes
No
No
No
Yes/ No
50 m br. shielded/ armored
Yes
Yes
Yes
4)
No
Yes/ Yes
VLT 8000 with RFI- filter (+
LC- module)
150m br. shielded/ armored
Yes
Yes
No
No
Yes/ Yes
Emission
Environment
Industrial environment
Housing, trades and light industries
VLT 8016- 8600/ 380- 480 V
VLT 8006- 8062/ 200- 240 V
Basic standard
EN 55011 Class A1
EN 55011 Class B
Setup
Motor cable
Conducted 150 kHz-
30 MHz
Radiated 30 MHz- 1 GHz
Conducted 150 kHz-
30 MHz
Radiated 30 MHz- 1 GHz
300 unshielded/ unarmored
No
No
No
No
VLT 8000 w/ o RFI filter option
150 m br. shielded/ armored
No
Yes
No
No
300 m unshielded / unarmored
Yes
1,2)
No
No
No
50 m br. shielded/ armored
Yes
Yes
Yes
1, 3)
No
VLT 8000 with RFI- module
150 m br. shielded/ armored
Yes
Yes
No
No
1) Does not apply to VLT 8450 - 8600.
2) Depending on installation conditions
3) VLT 8042- 8062, 200- 240 V and VLT 8152-8302 with external filter
4) Does not apply to VLT 8011 (380-480 V)
In order to minimize the conducted noise to the line supply and the radiated noise from the AFD system, the motor cables should be as short as possible and the shield ends should
be made in accordance with the section on electrical installation.
M
G
.80.
A7.
22
-
VLT
is
a
re
g
ist
er
ed
Danfo
s
s
tra
de
mar
k
188
Rosewood STP ST42 General (Operation and Maintenance Manual - Part 4:
Section 6.3 Manufacturers Manuals 6.3.33 Danfoss VLT Aquadrive 8000) Vendor Manual
QP Id: VM207
Active: 03/09/2013
Page 194 of 208