4. MOUNTING
4-2
IMS01T28-E4
4.1 Mounting Cautions
This chapter describes installation environment, mounting cautions, dimensions and mounting procedures.
(1)
This instrument is intended to be used under the following environmental conditions.
(IEC 61010-1)
[POLLUTION DEGREE 2]
(2)
Use this instrument within the following environment conditions:
Allowable ambient temperature:
10 to
50
C
Allowable ambient humidity:
5 to 95 %RH
(Absolute humidity: MAX.W.C
29 g/m
3
dry air at 101.3 kPa)
Installation environment conditions:
Indoor use
Altitude up to 2000 m
(3)
Avoid the following conditions when selecting the mounting location:
Rapid changes in ambient temperature which may cause condensation.
Corrosive or inflammable gases.
Direct vibration or shock to the mainframe.
Water, oil, chemicals, vapor or steam splashes.
Excessive dust, salt or iron particles.
Excessive induction noise, static electricity, magnetic fields or noise.
Direct air flow from an air conditioner.
Exposure to direct sunlight.
Excessive heat accumulation.
(4)
Mount this instrument in the panel considering the following conditions:
Provide adequate ventilation space so that heat does not build up.
Do not mount this instrument directly above the equipment that generates large amount of heat (heaters,
transformers, semi-conductor functional devices, large-wattage resistors).
If the ambient temperature rises above 50
C, cool this instrument with a forced air fan, cooler, etc.
Cooled air should not blow directly on this instrument.
In order to improve safety and the immunity to withstand noise, mount this instrument as far away as
possible from high voltage equipment, power lines, and rotating machinery.
High voltage equipment: Do not mount within the same panel.
Power lines:
Separate at least 200 mm
Rotating machinery:
Separate as far as possible
Space required between each module vertically
When the module is mounted on the panel, allow a
minimum of 50 mm at the top and bottom of the module
to attach the module to the mainframe.
50 mm or more
To prevent electric shock or instrument failure, always turn off the power before
mounting or removing the instrument.
WARNING
!
Содержание Z-TIO-G
Страница 8: ...i 6 IMS01T28 E4 MEMO...
Страница 16: ...IMS01T28 E4 1 8 MEMO...
Страница 22: ...2 6 IMS01T28 E4 MEMO...
Страница 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Страница 52: ...5 14 IMS01T28 E4 MEMO...
Страница 82: ...7 18 IMS01T28 E4 MEMO...
Страница 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Страница 216: ...10 6 IMS01T28 E4 MEMO...
Страница 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Страница 230: ...11 14 IMS01T28 E4 MEMO...
Страница 244: ...A 4 IMS01T28 E4 MEMO...
Страница 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...