9. COMMUNICATION DATA DESCRIPTION
IMS01T28-E4
9-98
PFF reference voltage
RKC communication
identifier
JP
Modbus
register address
042BH (1067)
The reference voltage of the Power feed forward (PFF) is set here.
Attribute:
R/W
Digits:
7 digits
Number of data:
1 (Data of each module)
Data range:
0.0 to 300.0 V
Factory set value:
0.0
Related parameters:
PFF power supply frequency (P. 9-95),
Power feed forward (PFF) selection (P. 9-96),
Measurement power supply frequency (P. 9-97), PFF input voltage (P. 9-97),
Output compensation factor for PFF reference voltage (P. 9-98),
Output compensation captured value for PFF reference voltage (P. 9-99),
PFF gain (P. 9-99)
Function:
Captures PFF input voltage as PFF reference voltage at the time of power-on,
switching the mode from STOP (control stop) to RUN (control start), and changing
the set value (SV).
This parameter is activated when the Power feed forward (PFF) input is used.
The PFF reference voltage is automatically taken in and set by the instrument under the normal
operation. Users do not need to set this parameter by themselves.
Output compensation factor
for PFF reference voltage
RKC communication
identifier
JQ
Modbus
register address
ch1: 042CH (1068)
ch2: 042DH (1069)
Set the output compensation factor of the Power feed forward reference voltage.
Attribute:
R/W
Digits:
7 digits
Number of data:
2 (Data of each channel)
Data range:
0.00 to 99.99
Factory set value:
1.00
Related parameters:
PFF power supply frequency (P. 9-95),
Power feed forward (PFF) selection (P. 9-96),
Measurement power supply frequency (P. 9-97), PFF input voltage (P. 9-97),
PFF reference voltage (P. 9-98),
Output compensation captured value for PFF reference voltage (P. 9-99),
PFF gain (P. 9-99)
This parameter is activated when the Power feed forward (PFF) input is used.
There is no need to set this parameter in normal operations.
Содержание Z-TIO-G
Страница 8: ...i 6 IMS01T28 E4 MEMO...
Страница 16: ...IMS01T28 E4 1 8 MEMO...
Страница 22: ...2 6 IMS01T28 E4 MEMO...
Страница 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Страница 52: ...5 14 IMS01T28 E4 MEMO...
Страница 82: ...7 18 IMS01T28 E4 MEMO...
Страница 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Страница 216: ...10 6 IMS01T28 E4 MEMO...
Страница 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Страница 230: ...11 14 IMS01T28 E4 MEMO...
Страница 244: ...A 4 IMS01T28 E4 MEMO...
Страница 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...