9. COMMUNICATION DATA DESCRIPTION
IMS01T28-E4
9-28
Link area number
RKC communication
identifie
LP
Modbus
register address
ch1: 00C2H (194)
ch2: 00C3H (195)
Memory area numbers for linking the corresponding memory areas are set when Ramp/Soak control is
performed.
Attribute:
R/W
Digits:
7
digits
Number of data:
2 (Data of each channel)
Data range:
0 to 8
(0:
No
link)
Factory set value:
0
Function:
Link area number is used for Ramp/Soak control function in conjunction with Area
soak time and Setting change rate limiter (up/down).
Area soak time of
memory area 1
Area soak time of
memory area 2
Setting change rate limiter
(down) of memory area 3
Area soak time of
memory area 3
Measured value (PV)
Set value (SV) of
memory area 2
Set value (SV) of
memory area 1
Set value (SV) of
memory area 3
Present set value (SV)
Time
Memory area 2
Memory area 3
Memory area 1
Setting change
rate limiter (up)
of memory area 2
Setting change
rate limiter (up)
of memory area 1
The area soak time for the memory area linked last becomes invalid to continue the state of the
Set value (SV) reached.
Содержание Z-TIO-G
Страница 8: ...i 6 IMS01T28 E4 MEMO...
Страница 16: ...IMS01T28 E4 1 8 MEMO...
Страница 22: ...2 6 IMS01T28 E4 MEMO...
Страница 34: ...4 MOUNTING 4 4 IMS01T28 E4 4 2 Dimensions Terminal type module 85 100 5 Unit mm 30 6 7...
Страница 52: ...5 14 IMS01T28 E4 MEMO...
Страница 82: ...7 18 IMS01T28 E4 MEMO...
Страница 211: ...TROUBLE SHOOTING IMS01T28 E4 10 1 10 1 Solutions for Problems 10 2...
Страница 216: ...10 6 IMS01T28 E4 MEMO...
Страница 217: ...SPECIFICATIONS IMS01T28 E4 11 1...
Страница 230: ...11 14 IMS01T28 E4 MEMO...
Страница 244: ...A 4 IMS01T28 E4 MEMO...
Страница 245: ...The first edition SEP 2012 IMQ00 The fourth edition FEB 2019 IMQ00...